Overrides
Temporary Override: After touching the OVERRIDE button from the Home Screen or adjusting the temperature setpoint, the
thermostat shall use a pre-set occupied temperature. The new temperature will be maintained for 1 hour and can be adjusted
up to the maximum override duration set by the installer.
Holiday Override: Selecting HOLIDAY MODE from the Menu shall allow the user to set setback temperatures from the current
day to a specified date.
Holiday Schedule: Selecting HOLIDAY SCHEDULE from the Menu shall allow the user to set US or Canadian Holidays and
Custom Events:
US or Canadian Holidays: The thermostat shall allow the user to customize temperature settings to be maintained on speci-
fied national holidays. The thermostat resumes normal scheduling between selected holidays.
Custom Events: The thermostat shall allow the user to customize temperature settings to be maintained during a specific
event. Up to 25 Custom Events can be setup for a specific date or a day in a month. The thermostat resumes normal sched-
uling after the event.
Initiate Occupancy: The thermostat shall keep the temperature at an energy saving level until the user touches "Press to Start
Occupancy" on the home screen. The thermostat returns to an energy saving level after the hold until time expires or the
Occupied period ends.
Remote Setback using an Occupancy Sensor (requires the equipment interface module): During an Occupied Period, the
thermostat shall override the program schedule and follow the desired standby settings when the occupancy sensor detects
the room is unoccupied. The thermostat shall resume the program schedule when the occupancy sensor detects the room is
occupied.
The thermostat provides three levels of keypad lockout to prevent changes to the thermostat: Unlocked, Partial Lockout and
Full Lockout.
The thermostat provides heating and cooling temperature range stops to limit temperature setpoint adjustments.
Reminders and Alarms
The thermostat shall provide an alert on the display when the HVAC filter requires replacement or cleaning.
The thermostat shall provide an alert on the display when maintenance is required on the humidification, dehumidification and
ventilation equipment.
The thermostat shall provide an alert on the display when a problem is detected by a dry contact device connected to the
sensor inputs (requires the equipment interface module).
The thermostat shall provide an alert on the display when service is required based on the Custom Reminders entered by the
installer. Custom Reminders are displayed based on date or when the outdoor temperature exceeds a level selected by the
installer.