User's Manual

Rev. 1 OWA 100 Adapter User Manual 29
September 2010
5. Maintenance/Repair
5.1 Parts
The following replacement parts may be ordered from Honeywell.
Part number Qty. Description
50056644-501 1 REMOTE MOUNTING KIT FOR 1/2 NPT OWA 100 ADAPTER
50056644-502 1 REMOTE MOUNTING KIT FOR M20 OWA 100 ADAPTER
30671907-001 1 PIPE MOUNT BRACKET KIT (SS) FOR MOUNTING OWA 100 ADAPTER
50026010-001 2 3.6V LITHIUM THIONYL CHLORIDE (Li-SOCI2) BATTERY
50026010-002 4 3.6V LITHIUM THIONYL CHLORIDE (Li-SOCI2) BATTERY
50026010-003 10 3.6V LITHIUM THIONYL CHLORIDE (Li-SOCI2) BATTERY
5.2 Replacing the battery
When to replace
When the OWA 100 Adapter displays a LOW BAT message, see OWA 100 Adapter display modes on
page 19, you have 2-4 weeks to replace both batteries before they expire. When batteries are removed or
expired, all OWA 100 Adapter data is retained in the OWA 100 Adapter’s non-volatile memory.
Tools required
#1 Phillips Screwdriver or 3/16” Slotted Screwdriver
Procedure
ATTENTION
The battery must be replaced only by a trained service technician.
WARNINGS
Risk of death or serious injury by explosion. Do not open OWA 100
Adapter enclosure when an explosive gas atmosphere is present.
The battery must not be changed in an explosive gas atmosphere.
The batteries used in this device may present a risk of fire or chemical
burn if mistreated. Do not recharge, disassemble, heat above 100°C
(212°F), or incinerate.
When installing the battery, do not snag the battery terminal on the clip
or the battery may be damaged. Do not apply excessive force.
Do not drop. Dropping the battery may cause damage. If a battery is
dropped, do not install the dropped battery into the OWA 100 Adapter.
Dispose of dropped battery promptly per local regulations or per the
battery manufacturer’s recommendations.
and