Installation Instructions

CPO-PC400-W/CPO-PC400-UW HVAC CONTROLLER
EN0B-0085 IE10 R0420 14
Cable Specifications
Power Supply Cable Specifications
The length of the power supply cable includes the length of
the cables to connected modules.
NOTE: The supply voltage must, in any case, be at least
19.2 Vac (24 Vac -20%).
See also the connection diagrams presented in Fig. 9
through Fig. 26 for details.
Antenna Cable Specifications
Field Device Power Supply Cable
Specifications
Communication Bus Cable Specifications
Use Belden 9841 or Equivalent cable with the following
specifications:
RS485 Bus Cable Specifications
An MSTP EIA-485 network shall use shielded, twisted-
pair cable with a characteristic impedance between 100
and 130 ohms.
Distributed capacitance between conductors shall be
less than 100 pF per meter (30 pF per foot).
Distributed capacitance between conductors and shield
shall be less than 200 pF per meter.
Table 22. Power Supply Cable Specifications
Device
Cable
Length
Cable cross-
section
CPO-PC400-W/
CPO-PC400-UW
Max. 3 m Min. 1.5 mm
2
Panel Bus I/O Max. 3 m Min. 1.5 mm
2
FBA Max. 20 m Min. 1.5 mm
2
EXPIO Max. 1200 m Min. 1.5 mm
2
CPO-DIO Max. 1200 m Min. 1.5 mm
2
C-Bus > 3 m Depends on Plug
Gauge. See
“Wiring
Terminals”
section on
page 13
M-Bus > 3 m Depends on Plug
Gauge. See
“Wiring
Terminals”
section on
page 13
Table 23. Antenna Cable Specifications
Device Cable Length
Cable cross-
section
Remote
Antenna
Max. 3 m
5 mm
2
Table 24. Field Device Power Supply (24 Vac) Cable
Specifications
Cable Length Cable Cross-section
≤ 100 m (300 ft.), single
transformer (see
“Example 1: Power Supply
via Controller Using Panel
Module” section on
page 12.)
min. 1.5 mm
2
(16 AWG)
≤ 400 m (1300 ft.),
separate transformers
(see “Example 2: Power
Supply via Separate
Transformer” section on
page 12.)
not allowed for > 100 m
(300 ft)
Table 25. Communication Cable Specifications
Interface (Buses) Cable Type
RS485 interfaces 1, 2, and
3 (Panel Bus, BACnet Bus,
Field Bus, Modbus, C-Bus,
M-Bus)
One or two pairs
(depending on the
application) of twisted
pair complying with
EIA485 standard (level IV,
22 AWG, solid core, non-
shielded), e.g., J-Y-Y 2 x 2 x
0.8, or shielded wire.
RS485 interface 4 (Panel
Bus, CP-IO Bus)
Ethernet 1, 2 (Ethernet
Bus)
CPO-PC400-W/CPO-
PC400-UW can be used
with CAT5, CAT6, and
CAT7 cabling. Standard
Ethernet cross-over cable,
Cat-5, min. 10/100
MBaud, max. length of
100 m