Installation Instructions

CPO-PC400-W/CPO-PC400-UW HVAC CONTROLLER
27 EN0B-0085 IE10 R0420
Connection to Field Bus Modules Powered by the Same Transformer as the CPO-PC400-
W/CPO-PC400-UW
This configuration is suitable for connecting FBAs which are all located in the same wiring cabinet as the CPO-PC400-
W/CPO-PC400-UW.
Fig. 18. Connection (L < 3 m) of RS485 interfaces 1, 2, or 3 (RS485 interface 1 shown) to a Field Bus
NOTES:
N = max. 31 unit loads. Normally, in this case (i.e. with a bus length of max. 3 m), it is not necessary to employ
termination resistors.
For communication cable lengths, transmission speeds, and termination, see “General Information on the
RS485 Standard” section on page 7. For fusing, see “Fusing” section on page 11.
TX
5V
GND
FBA #1
Isolaon
Barrier
RX
5V_ISO
GND_ISO
RS485+
RS485-
R
T
110VAC/230VAC
24VAC
FBA #N
F1
Field Bus +
Field Bus -
24VAC-COM
L < 3m
R
T
24VAC
Field Bus +
Field Bus -
24VAC-COM
24VAC
Shielding
Oponal
FGND
24V0
24V~
CH1+
CH1-
GND1
CPO-PC400-W/CPO-PC400-UW