Installation Instructions

CPO-PC400-W/CPO-PC400-UW HVAC CONTROLLER
31 EN0B-0085 IE10 R0420
Connection to a CP-IO Bus Powered by a Same Transformer
Fig. 22. Connection (L < 3 m) of RS485 interface 4 to a CP-IO Bus
NOTES:
* The 24V~ and 24V0 terminals at RS485-4 Interface have an automatic resetting fuse protection. For more
information, see “Wireless Connectivity” section on page 15.
NOTES: N = max. 9 modules. The mode switch of the integrated termination resistor of the final CP-DIO (CP-
DIO #N) must be set to “ON.” If the last module is CP-EXPIO, the end of line resistor must be included.
For communication cable lengths, transmission speeds, and termination, see “General Information on the
RS485 Standard” section on page 7. For capacity restrictions, see “Connection to CP-IO Bus” section on
page 10. For fusing, see “Fusing” section on page 11.
CP-DIO/EXPIO #1
110VAC/230VAC
24VAC
F1
FGND
24V0
24V~
L < 3m
CP-DIO/EXPIO #N
FGND
485-
485+
N24 VAC
S24 VAC
FGND
FGND
485-
485+
N24 VAC
S24 VAC
FGND
R
T
R
T
TX
5V
GND
Isolaon
Barrier
RX
5V_ISO
~
0
-
+
GND_ISO
RS485-
RS485+
FGND
GND
CPO-PC400-W/CPO-PC400-UW