Overview of Primary Product

V5011N TWO-WAY THREADED GLOBE VALVE
63-2548—3 6
Mounting
The preferred valve mounting position is with the stem
vertical. For steam applications, mount with the stem at a 45
degree angle. Do not mount the valve with the stem more than
90 degrees from the vertical (pointing lower than horizontal).
Scale and foreign material can collect, scoring the stem and
causing packing leakage. Protect the stem from damage due
to bending or scratching.
IMPORTANT
1. Before installing linkage and actuator, make sure that
the valve stem operates freely. Impaired stem
operation can indicate that the body was twisted or
the stem was bent. Either of these conditions can
require valve replacement.
2. Align pipes squarely with valve at each end connection.
3. If the pipes are forced into the valve, the body can
become twisted and improper seating can result.
4. Apply pipe dope sparingly.
5. Be careful to prevent pipe debris, such as chips and
scale, from entering the piping because this material
can lodge in the seat and prevent proper closing.
NOTE: Threading on threaded bodies conform to NPT.
Refer to the table in Fig. 4 for valve pipe sizes and thread
lengths. Fig. 4 also shows two effective methods of holding
the valve and pipe when attaching it. Refer to installation
information furnished with the linkage and motor when
installing these controls.
Table 2. Close-off Ratings (psid) for V5011N Valves with Electric/Electronic Actuators.
a
Pressure is limited by fluid temperature. See valve temperature/pressure ratings.
Fig. 4. Installing valves with threaded connections.
Valve Size (NPT)
Mod IV Motor with Q5001 Linkages
ML6421A,
ML7421A
ML6425, ML7425
ML6420, ML7420 ML7984, ML6874
320 lb 160 lb 80 lb 405 lb 135 lb 160 lb
V5011N1xxx and V5011N3xxx Valves
1/2
230
a
230
a
230
a
230
a
3/4
230
a
131
1
230
a
196 91
230
a
163 196
1-1/4
230
a
126 57
230
a
104 126
1-1/2 173 81 36 221 67 81
2 984619126 37 46
V5011N2xxx Valves
1/2, 3/4
100
a
100
a
100
a
100
a
1
100
a
100
a
91
100
a
1-1/4
100
a
100
a
57
1-1/2
100
a
81 36
100
a
67 81
2984619
100
a
37 46
USE VISE GRIPS WITH THE HEX END NEXT TO THE PIPE
(DO NOT TWIST OR SQUEEZE VALVE BODY).
USE VISE TO HOLD PIPE SECURELY TO PREVENT TURNING. USE
PARALLEL-JAW WRENCH TO GRIP VALVE HEX FLATS NEXT TO PIPE
M11763
USE PROPERLY REAMED AND CLEANED PIPE AND
MODERATE AMOUNT OF DOPE (LEAVE TWO THREADS BARE).
PIPE SIZE
(IN.)
1/2
3/4
1
1-1/4
1-1/2
2
EFFECTIVE LENGTH OF THREADS
IN IN. (MM)
1/2
9/16
11/16
11/16
11/16
3/4
(12.7)
(14.3)
(17.5)
(17.5)
(17.5)
(19.1)
1
1
2
2
3
3