User Guide

Table Of Contents
Honeywell LonWorks Interface 23
Example2
Read parameter number 112 (Nominal speed of the motor “Basic Application par. ID112”)
default value 1440 (1440 rpm).
Read command to nviParSet
- LN_RECALL 112 <x x x x> x x x x
If the read command is successful then nvoParOut value is
- LN_RECALL 112 <0 0 5 A0> 0 0 0 0
If the read command fails then nvoParOut value is
- LN_ LN_NUL 112 <0 0 0 0> 0 0 0 0
6.3 Output Network Variables
Function Variable Name SNVT type Min. Value Max. Value
Node Object status nvoStatus SNVT_obj_status
Drive speed feedback nvoDrvSpeed SNVT_lev_percent -163.840% +163.830%
Actual motor current nvoDrvCurnt SNVT_amp 0.0A 3276.7A
Actual drive power nvoDrvPwr SNVT_power_kilo 0,0 kW 6553,5 kW
Drive total running hours
nvoDrvRunHours SNVT_time_hour 0 h 65535
Status word nvoDrvStatus SNVT_state n/a n/a
kWh trip counter nvoDrvEnrgy SNVT_elect_kwh 0kWh 65535kWh
Active fault code nvoActFault SNVT_count 0 41
Process Out nvoProcessOut1..8 SNVT_ lev_percent 0 65535
Digital Out nvoDigitalOut1..8 SNVT_switch 0 4
Parameter Out nvoParResp SNVT_preset - -
Table 10. Network output variables
NvoStatus
This output network variable reports the status for Node object or Variable Speed Motor Drive
object.