Honeywell BACnet Commissioning 53
AV27
Maximum Frequency Maximum Frequency
Hz W
AV28
Accel Time Acceleration Time
seconds W
AV29
Decel Time Deceleration Time
seconds W
AV30
FBProcessDataIN 1 Application specific
-32768.0 to +32767.0
resolution 1.0
C
AV31
FBProcessDataIN 2 Application specific
-32768.0 to +32767.0
resolution 1.0
C
AV32
FBProcessDataIN 3
Application specific
-32768.0 to +32767.0
resolution 1.0
C
AV33
FBProcessDataIN 4
Application specific
-32768.0 to +32767.0
resolution 1.0
C
AV34
AnyParam ID
ID number that is used
in AV35
0.0 to 65535.0
resolution 1.0
W
AV35
AnyParam Value
Value of ID defined by
AV34
-32768.0 to +32767.0
resolution
W
AV36
FBFixedControlWord PDI 0 1) (see next page)
C
AV37
FBGeneralControlWord PDI 1 2) (see next page)
C
AV38
FBFixedStatusWord PDO 0 3) (see next page)
R
AV39
FBGeneralStatusWord PDO 1 4) (see next page)
R
NOTE: For Present Value Access Types, R = Read-only, W = Writeable, C = Commandable.
Commandable values support priority arrays & relinquish defaults.
Note: These Analog Value objects are introduced in BACnet SW version:
OPTCJ_10522V009.vcn
1) FBFixedControlWord PDI 0, bit encoding (All-in-One Applications)
B0=RUN; 0=Stop, 1=Run
B1=DIRECTION; 0=Fwd, 1=Rev
B2=FaultRST; Reset on rising edge
B3-15 Application Specific
2) FBGeneralControlWord PDI 1, bit encoding
Application Specific
3) FBFixedStatusWord (MCStatus) PDO 0, bit encoding
B0=Ready; 0=not ready, 1=ready
B1=Run; 0=stopped, 1=running
B2=Direction; 0=clockwise, 1=counterclockwise
B3=Fault; 1=the FC is faulted and stopped (?)
B4=Warning; 1=warning
B5=AtReference; 1=at reference speed
B6=ZeroSpeed; 1=at zero speed
B7=FluxReady; 1=flux ready
B8=TCSpeedLimitActive;
B9=DetectedEncoderDirection;
B10=UVFastStop;
B11=DC brake status 1=DC brake active
B12-15 Firmware Specific
* Not all the bits are supported in every application