Specifications

Motorized Zone Valves
70-6910 237
Home
Controls Indoor Air Quality
Residential
Combustion Controls
Hydronic Controls
Water
Controls Building Automation
Commercial
Components Pneumatic Controls
Industrial Combustion
Controls
V8044 Low Voltage Diverting Valves
On-off and diverting low voltage valves consist of an actuator and
valve assembly for controlling the flow of hot water.
Manual opener (on all models, except straight-through, normally
open valves) for valve operation on power failure; valve returns to
automatic position when power is restored.
All models may be installed without disassembling the valve.
Compact construction for easy installation.
Complete powerhead may be removed or replaced without breaking
plumbing line connections or draining the system.
Actuator motor may be replaced without removing the valve body or
draining the system.
Dimensions Diagram: See page 230
Application: Hydronic Control
Type: 2 position
Body Pattern: 3-Way, Diverting
Valve Action: Spring Return
Voltage: 24 Vac
Frequency: 60 Hz; 50 Hz
Power Consumption: 7.7 VA
Nominal Timing (sec, min): 30 sec
De-energized Position: Port A Normally Closed
Electrical Connections: 18 in. leads (457 mm leads)
Static Pressure: 125 psi (862 kPa)
Fluid Temperature Range: 40 F to 200 F (5 C to 93 C)
Maximum Ambient Temperature: 125 F (52 C)
Comments: Use this valve in closed loop hydronic systems that do not
contain dissolved oxygen in system water, such as fresh water from
frequent source of makeup water.
Valve designed for cycling (not constantly powered on) applications.
Materials
(Body): Brass
(Stem): Stainless Steel
(Seat): Brass
(Packing O-Ring): EPDM rubber
(Ball Plug): Buna-N (NBR) Rubber Ball
Approvals:
Underwriters Laboratories, Inc. UL Component Listed: File MH11826
Vol. 1
Replacement Parts:
802360JA 24V, 50/60 Hz Replacement motor for V8043, V8044 Zone
Valves
802360UA 24V, 50/60 Hz Replacement motor for steam and heating
Zone Valves
Flare Connection NPT Connection Sweat Connection Sweat Connection Sweat Connection
Product Number
Pipe Size Capacity
Connection
Type
Auxiliary
End
Switch
Maximum Close-
off Pressure
Includes
Manual
Opener(inch) DN (Cv) (Kv) (psi) (kPa)
V8044A1002 1/2 in. DN15 4 Cv 3.4 Kv Flare 20 psi 138 kPa Yes
V8044A1010 1/2 in. DN15 4 Cv 3.4 Kv Sweat 20 psi 138 kPa Yes
V8044A1044 3/4 in. DN20 7.0 Cv 6 Kv Sweat 10 psi 69 kPa Yes
V8044A1051 1/2 in. DN15 4 Cv 3.4 Kv Sweat 20 psi 138 kPa Restricted 2.5 Cv bypass port. Yes
V8044A1135 1/2 in. DN15 4 Cv 3.4 Kv NPT 20 psi 138 kPa Yes
V8044A1143 3/4 in. DN20 4 Cv 3.4 Kv NPT 20 psi 138 kPa Yes
V8044B1018 1/2 in. DN15 4 Cv 3.4 Kv Sweat 20 psi 138 kPa Integral SPDT changeover
Aquastat controller
Yes
V8044E1003 1/2 in. DN15 4 Cv 3.4 Kv Sweat SPST 20 psi 138 kPa Yes
V8044E1011 3/4 in. DN20 7.0 Cv 6 Kv Sweat SPST 10 psi 69 kPa Yes