Home Security System User Manual
Table Of Contents
- ONYX®FirstVision™
- Fire Alarm System Limitations
- Installation Precautions
- FCC Warning
- Section 1 Introduction
- Section 2 FirstVision Installation Instructions
- Section 3 Enabling FirstVision to Monitor Your Building
- 3.1 Process Overview
- 3.2 Make Connections to FirstVision
- 3.3 Turn on Power to FirstVision
- 3.4 Set the FirstVision Clock and Time Zone
- 3.5 Establish Communication Between Your LAN and FirstVision
- 3.6 Establish Gateway Communication
- 3.7 Copy Your Exported Building Design to FirstVision
- 3.8 Display Your Building Design on FirstVision
- 3.9 Test Your Building Design on FirstVision
- 3.10 Touch Screen Calibration
- Section 4 Operating Basics of FirstVision
- 4.1 Normal Operation (No Events Being Reported)
- Figure 4.1 FirstVision Display Example: No Alarms
- Figure 4.2 FirstVision Display Example: Floor Number Button
- Figure 4.3 FirstVision Display Example: Building Information
- Figure 4.4 FirstVision Display Example: Zoomed Floor Plan
- Figure 4.5 FirstVision Display Example: Moving Through a Zoomed Floor Plan
- Figure 4.6 FirstVision Display Example: HAZMAT Information
- 4.2 Investigating Gateway Disconnection
- 4.3 Operation When a Fire Alarm is Received
- 4.4 Operation After a Fire Alarm Has Been Cleared
- 4.5 Accessing the Log File
- 4.1 Normal Operation (No Events Being Reported)
- Section 5 The Development of FirstVision
- 5.1 The Current Situation for a Firefighter
- 5.2 The Technology of FirstVision
- 5.3 Expected Firefighter Interaction with the FirstVision
- 5.3.1 Example Emergency Situations
- Figure 5.1 Fire Scene Scenario Floor Plan Information
- Figure 5.2 Fire Scene Scenario Roof Plan Information
- Figure 5.3 Fire Scene Scenario HAZMAT Information
- Figure 5.4 Fire Scene Scenario Building Information
- Figure 5.5 Example Building Site Plan Information
- Figure 5.6 Example HAZMAT Information
- Figure 5.7 Example Contact Information
- 5.3.1 Example Emergency Situations
- Index
11FIRSTVISION™ Installation and Operation Manual - P/N: 53034:Rev: A2 10/29/07
Section 2 FIRSTVISION Installation Instructions
2.1 Power Sources and Outputs Overview
• Complete all mounting procedures and check all wiring before applying power.
• Electrical connections include the following:
• Primary Power Source: +24VDC, delivered through a power supply listed for fire protection
services.
• Secondary Power Source: +24VDC, delivered from batteries.
NOTE: You can use this information to install the FIRSTVISION enclosure (“Enclosure Installation”
on page 12) and to make power supply connections to the enclosure’s control board, or you can
refer to the ONYX®FIRSTVISION™ Enclosure Installation Instructions (P/N 53105).
Table 2.1 Power Supply Required Ranges
TYPICAL
Input Voltage 24V
Input Current @24V 3A
!
WARNING: Power Sources
Remove all power sources to equipment while connecting electrical components. Leave the
external, main power breaker OFF until installation of the LCD is complete.
NOTE: FIRSTVISION LCD requires +24VDC @3A nominal and supervised battery backup in
accordance with local code requirements. It can be powered by any regulated, power limited
source that is approved for use with fire protective signaling units by a regulatory agency.