# ISU ISU Name ISU Options (defaults in bold) Notes
370 Heat 1 CPH
(Heating cycle
rate stage 1)
1 - 12 CPH This ISU is only displayed when Heat Stages is set to 1 stage or more stages. Cycle rate limits
the maximum number of times the system can cycle in a 1 hour period measured at a 50%
load. For example, when set to 3 CPH, at a 50% load, the most the system will cycle is 3 times
per hour (10 minutes on, 10 minutes off). The system cycles less often when load conditions
are less than or greater than a 50% load. The recommended (default) cycle rate settings are
below for each heating equipment type:
Standard Efficiency Gas Forced Air = 5 CPH; High Efficiency Gas Forced Air = 3 CPH; Oil
Forced Air = 5 CPH; Electric Forced Air = 9 CPH; Fan Coil = 3 CPH; Hot Water Radiant Heat
= 3 CPH; Steam = 1 CPH.
371 Heat 2 CPH
(Heating cycle
rate stage 2)
1 - 12 CPH This ISU is only displayed when Heat Stages is set to 2 stages. The recommended (default)
cycle rate settings are below for each heating equipment type:
Standard Efficiency Gas Forced Air = 5 CPH; High Efficiency Gas Forced Air = 3 CPH; Oil
Forced Air = 5 CPH; Electric Forced Air = 9 CPH; Fan Coil = 3 CPH; Hot Water Radiant Heat
= 3 CPH; Steam = 1 CPH.
375 Aux Heat CPH
(Heating cycle
rate Auxiliary
Heat)
1 - 12 CPH This ISU is only displayed when ISU 200 = Heat Pump and ISU 221=1. It is only displayed when
Auxiliary Heat is configured. The recommended cycle rate settings are below for each heating
equipment type:
Standard Efficiency Gas Forced Air = 5 CPH; High Efficiency Gas Forced Air = 3 CPH; Oil
Forced Air = 5 CPH; Electric Forced Air = 9 CPH.
425 Smart Response On, Off Smart Response is a comfort setting. Heating or cooling equipment will turn on earlier, ensur-
ing the indoor temperature will match the setpoint at the scheduled time.
429 Max Cool
Temperature
from Min. Cool Temp. to 99 °F or to 37.0 °C (90 °F
or 32 °C)
The user cannot set the cooling temperature above this level.
430 Min Cool
Temperature
from 50 °F or 10.0 °C to Max. Cool Temp. (50 °F
or 10 °C)
The user cannot set the cooling temperature below this level.
431 Max Heat
Temperature
from Min. Heat Temp. to 90 °F or to 32.0 °C (90 °F
or 32 °C)
The user cannot set the heating temperature above this level.
432 Min Heat
Temperature
from 40 °F or 4.4 °C to Max. Heat Temp. (50 °F
or 10 °C)
The user cannot set the heating temperature below this level.
702 Air Filters 0 - 2 This ISU refers to the number of air filters in the system.
711 Air Filter 1
Reminder
Off
10, 20, 30, 45, 60, 90, 120, 150 Run Time Days
30, 45, 60, 75 Days
3, 4, 5, 6, 9, 12, 15 Months
Choose either calendar or equipment run time-based reminder.
712 Air Filter 2
Reminder
Off
10, 20, 30, 45, 60, 90, 120, 150 Run Time Days
30, 45, 60, 75 Days
3, 4, 5, 6, 9, 12, 15 Months
Choose either calendar or equipment run time-based reminder.
810 Hum Pad
Reminder
Off
6, 12 Calendar Months
921 Dehum Filter
Reminder
Off
30, 60 Calendar Days
3 - 12 Calendar Months (in 1 month increments)
1018 Vent Filter
Reminder
Off, 3, 6, 9, 12 months
1100 UV Devices 0 - 2 Some systems may have two UV devices, one for the ACoil and another for Air Treatment. A
replacement reminder can be setup for each one separately.
1105 UV Bulb 1
Reminder
Off, 6, 12, 24 months
1106 UV Bulb 2
Reminder
Off, 6, 12, 24 months
1401 Idle Brightness 0= Off, 0 - 5 Adjust brightness of an inactive backlight (idle screen) from default 0 (backlight off) to 5
(maximum
brightness).
1410 Clock Format 12 hour, 24 hour
1415 Daylight Saving On, Off Set to Off in areas that do not follow Daylight Saving Time.