Spec Sheet

GENERATOR MODEL G007059-1 (16 KW) MODEL G007062-1 (20 KW) MODEL G007065-2 (22 KW)
Rated Maximum Continuous Power Capacity (LP) 16,000 Watts* 20,000 Watts* 22,000 Watts*
Rated Maximum Continuous Power Capacity (NG) 16,000 Watts* 18,000 Watts* 19,500 Watts*
Rated Voltage 240 240 240
Rated Maximum Continuous Load Current – 240 V (LP/NG) 66.7/66.7 83.3/75.0 91.6/81.3
Total Harmonic Distortion Less than 5% Less than 5% Less than 5%
Main Line Circuit Breaker 70 Amp 90 Amp 100 Amp
Phase 1 1 1
Number of Rotor Poles 2 2 2
Rated AC Frequency 60 Hz 60 Hz 60 Hz
Power Factor 1.0 1.0 1.0
Battery Requirement (not included) 12 Volts, Group 26R 540 CCA Minimum or Group 35AGM 650 CCA Minimum
Unit Weight (lb/kg) 409/186 448/203 466/211
Dimensions (L x W x H) in/mm 48 x 25 x 29 / 1218 x 638 x 732
Sound output in dB(A) at 23 ft (7 m) with generator operating at normal load** 67 67 68
Sound output in dB(A) at 23 ft (7 m) with generator in WhisperCheck™ low speed exercise** 55 55 59
Exercise duration 5 min 5 min 5 min
ENGINE
Type of Engine GENERAC GFORCE 1000 SERIES
Number of Cylinders 2 2 2
Displacement 999 cc 999 cc 999 cc
Cylinder Block Aluminum w/ Cast Iron Sleeve Aluminum w/ Cast Iron Sleeve Aluminum w/ Cast Iron Sleeve
Valve Arrangement Overhead Valve Overhead Valve Overhead Valve
Ignition System Solid-state w/ Magneto Solid-state w/ Magneto Solid-state w/ Magneto
Governor System Electronic Electronic Electronic
Compression Ratio 9.5:1 9.5:1 9.5:1
Starter 12 VDC 12 VDC 12 VDC
Oil Capacity Including Filter Approx. 1.9 qt/1.8 L Approx. 1.9 qt/1.8 L Approx. 1.9 qt/1.8 L
Operating RPM 3,600 3,600 3,600
Fuel Consumption
Natural Gas ft³/hr (m³/hr)
1/2 Load 210 (5.95) 204 (5.78) 228 (6.46)
Full Load 305 (8.64) 301 (8.52) 327 (9.26)
Liquid Propane ft³/hr (gal/hr) [l/hr]
1/2 Load 74 (2.03) [7.70] 87 (2.37) [8.99] 92 (2.53) [9.57]
Full Load 107 (2.94) [11.11] 130 (3.56) [13.48] 142 (3.90) [14.77]
Note:
Fuel pipe must be sized for full load. Required fuel pressure to generator fuel inlet3.57” water column (713 mm mercury) for natural gas, 1012” water column (1922 mm mercury) for LP gas.
For BTU content, multiply ft
3
/hr x 2500 (LP) or ft
3
/hr x 1000 (NG). For Megajoule content, multiply m³/hr x 93.15 (LP) or m³/hr x 37.26 (NG)
CONTROLS
TwoLine Plain Text Multilingual LCD Display Simple user interface for ease of operation.
Mode Buttons: Auto Automatic Start on Utility failure. 7 day exerciser.
Manual Start with starter control, unit stays on. If utility fails, transfer to load takes place.
Off Stops unit. Power is removed. Control and charger still operate.
Ready to Run/Maintenance Messages Standard
Engine Run Hours Indication Standard
Programmable start delay between 21500 seconds Standard (programmable by dealer only)
Utility Voltage Loss/Return to Utility Adjustable (Brownout Setting) From 140171 V/190216 V
Future Set Capable Exerciser/Exercise Set Error Warning Standard
Run/Alarm/Maintenance Logs 50 Events Each
Engine Start Sequence Cyclic cranking: 16 sec on, 7 rest (90 sec maximum duration).
Starter Lock-out Starter cannot re-engage until 5 sec after engine has stopped.
Smart Battery Charger Standard
Charger Fault/Missing AC Warning Standard
Low Battery/Battery Problem Protection and Battery Condition Indication Standard
Automatic Voltage Regulation with Over and Under Voltage Protection Standard
UnderFrequency/Overload/Stepper Overcurrent Protection Standard
Safety Fused/Fuse Problem Protection Standard
Automatic Low Oil Pressure/High Oil Temperature Shutdown Standard
Overcrank/Overspeed (@ 72 Hz)/rpm Sense Loss Shutdown Standard
High Engine Temperature Shutdown Standard
Internal Fault/Incorrect Wiring Protection Standard
Common External Fault Capability Standard
Field Upgradable Firmware Standard
**Sound levels are taken from the front of the generator. Sound levels taken from other sides of the generator may be higher depending on installation parameters. Rating definitions - Standby: Applicable for supplying emergency power for the duration
of the utility power outage. No overload capability is available for this rating. (All ratings in accordance with BS5514, ISO3046 and DIN6271). * Maximum wattage and current are subject to and limited by such factors as fuel BTU/megajoule content,
ambient temperature, altitude, engine power and condition, etc. Maximum power decreases about 3.5 percent for each 1,000 feet (304.8 meters) above sea level; and also will decrease about 1 percent for each 6 °C (10 °F) above 16 °C (60 °F).
16 / 20 / 22 kW
Application & Engineering Data