Programming Manual

PROGRAMMING FORM
Entries apply to the ADEMCO VISTA-15P/VISTA-15PSIA and ADEMCO VISTA-20P/VISTA-20PSIA controls, except entries
shown in dashed
boxes, which apply only to the VISTA-20P/VISTA-20PSIA (partition entries) and are not applicable to the VISTA-15P/VISTA-15PSIA. In addition,
where noted, certain fields have special settings when used with the VISTA-20PSIA/VISTA-15PSIA (indicated by V20PSIA/V15PSIA with heavy
borders and reverse type throughout for easy identification).
Entry of a number other than one specified will give unpredictable results. Values shown in brackets are factory defaults.
SIA Guidelines: Notes in certain fields give instructions for programming the VISTA-20P/VISTA-15P for False Alarm Reduction.
20 Installer Code
[4112] | | |
4 digits, 0–9
21 Quick Arm Enable
[0,0]
0 = no; 1 = yes Part. 1 Part.2
22 RF Jam Option
[0]
0 = no RF Jam detection; 1 = send RF Jam report
UL: must be 1 if wireless devices are used
23 Quick (Forced) Bypass
[0,0]
0 = no quick bypass
UL: must be “0”
Part. 1 Part. 2
1 = allow quick bypass (code + [6] + [#] )
24 RF House ID Code
[00,00,00]
| | |
00 = disable all wireless keypad usage Part. 1 Part. 2 Common
01–31 = using 5827, 5827BD or 5804BD keypad
26 Chime By Zone
[0]
0 = no; 1 = yes (list chime zones on zone list 3 using *81 Menu mode)
27
Powerline Carrier Device (X–10)
[0]
House Code
0 = A; 1 = B; 2 = C; 3 = D; 4 = E; 5 = F; 6 = G; 7 = H; 8 = I; 9 = J;
#10 = K; #11 = L; #12 = M; #13 = N; #14 = O; #15 = P
UL: not for fire or UL installations
28 Access Code For Phone Module [00]
|
00 = disable;
(Partition 1 only)
1st digit: enter 1–9; 2nd digit: enter # + 11 for "
", or # + 12 for "#".
UL: must be “00” for UL Commercial Burg. installations
29 Long Range Radio Output
[0]
0 = disable; 1 = enable
31 Single Alarm Sounding Per Zone
[0]
0 = unlimited sounding; 1 = one alarm sounding per zone
V20PSIA/V15PSIA: If “0” selected, “alarm sounding per zone” will be
the same as the “number of reports in armed period” set in field *93 (1
if one report, 2 if 2 reports, unlimited for zones in zone list 7).
32 Fire Alarm Sounder Timeout
[0]
0 = sound stops at timeout; 1 = no timeout UL: must be “1” for fire install.
33 Alarm Sounder (Bell) Timeout
[1]
0 = none; 1 = 4 min; 2 = 8 min; 3 =12 min; 4 = 16 min;
UL: For residential fire alarm installation, must be set for a
minimum of 4 min (option 1); for UL Commercial Burglary
installations, must be minimum 16 min (option 4)
34 Exit Delay
[60,60]
| |
00 - 96 = 0 - 96 secs; 97 = 120 secs Part. 1 Part. 2
SIA Guidelines: minimum exit delay is 45 seconds
V20PSIA/V15PSIA: 45 - 96 = 45 - 96 secs; 97 = 120 secs
NOTE: Entries less than 45 will result in a 45-second delay.
UL: see inst. instr. for requirements. Common zones use part. 1 delay.
35 Entry Delay #1
[30,30]
| |
Common zones use same delay as partition 1.
Part. 1 Part. 2
00 - 96 = 0 - 96 seconds; 97 = 120 secs; 98 = 180 secs; 99 = 240 secs
SIA Guidelines: minimum entry delay is 30 seconds
V20PSIA/V15PSIA:
30-96 = 30 - 96 secs; 97 = 120 secs; 98 = 180 secs; 99 = 240 secs
NOTE: Entries less than 30 will result in a 30-second delay.
For UL Residential Burglary Alarm installations, must be set for a
maximum of 30 seconds; entry delay plus dial delay should not
exceed 1 min. For UL Commercial Burglar Alarm, total entry delay
may not exceed 45 seconds.
36 Entry Delay #2
[30,30]
| |
See *35 Entry Delay 1 for entries. Part. 1 Part. 2
37 Audible Exit Warning
[1,1]
0 = no; 1 = yes (SIA Guidelines: must be enabled) Part. 1 Part. 2
V20PSIA/V15PSIA: feature always enabled; field does not exist
38 Confirmation Of Arming Ding
[0,0]
0 = no; 1 = yes (wired keypads and RF) Part. 1 Part. 2
2 = yes, RF only
UL: must be “1” for UL Commercial Burglar Alarm inst.
39 Power Up In Previous State
[1]
0 = no, always power up disarmed; 1 = yes, power up in previous state
UL: must be “1” SIA Guidelines: must be “1”
DIALER PROGRAMMING (
40 –
42)
Do not fill unused spaces. Enter 0–9; #+11 for '
'; #+12 for '#'; #+13 for a 2-
second pause. If fewer than the maximum digits entered, exit the field by
pressing []. The next data field number is displayed.
40 PABX Access Code or
| | | | |
Call Waiting Disable Enter up to 6 digits. To clear entries,
press 40. If call waiting is used, enter call waiting disable digits “
(#+11) 70” plus “# + 13” (pause).
NOTES: 1. The call waiting disable feature cannot be used on a PABX line.
2. Using Call Waiting Disable on a non-call waiting line will
prevent successful communication to the central station.
V20PSIA/V15PSIA: If call waiting is used, enter call waiting disable digits
as described above, and also set Call Waiting Disable option in field *91.
41 Primary Phone No.
| | | | | | | | | | | | | | | | | | |
42 Second Phone No.
| | | | | | | | | | | | | | | | | | |
Enter up to 20 digits. To clear entries, press
41
or
42
respectively
.
NOTE:
For fields *43 thru *46: Enter 0–9; #+11 for B; #+12 for C; #+13 for D;
#+14 for E; #+15 for F. Enter [
]
as the fourth digit if a 3-digit account number
(for 3+1 dialer reporting format) is used. Enter 0 as the first digit of a 4-digit
account number for Nos. 0000-0999. Exit field by pressing
if only 3 digits are
used. E.g., For Acct. B234, enter: #+11 + 2 + 3 + 4
43 Partition 1 Primary Acct. No.
| | | / | | | | |
[FFFFFFFFFF] Enter 4 or 10 digits, as
chosen in *48 Report Format. See box above. To clear entries, press
*
43
*.
44 Part. 1 Secondary Acct. No. (see field *43 for entries)
| | | / | | | | | [FFFFFFFFFF] To clear, press
*
44
*
.
45 Partition 2 Primary Acct. No. (see field *43 for entries)
| | | / | | | | | [FFFFFFFFFF] To clear, press
*
45
*
.
46 Partition 2 Secondary Acct. No. (see field *43 for entries)
| | | / | | | | | [FFFFFFFFFF] To clear, press
*
46
*
.
47 Phone System Select [1]
If Cent. Sta. is not
on a WATS line: 0=Pulse Dial; 1=Tone Dial;
if Cent. Sta. is on
a WATS line: 2 = Pulse Dial ; 3 = Tone Dial
48 Report Format [77]
0 = 3+1, 4+1 ADEMCO L/S STANDARD primary secondary
1 = 3+1, 4+1 RADIONICS STANDARD
2 = 4+2 ADEMCO L/S STANDARD
3 = 4+2 RADIONICS STANDARD
5 = 10-digit ADEMCO CONTACT ID® REPORTING
6 = 4+2 ADEMCO EXPRESS
7 = 4-digit ADEMCO CONTACT ID® REPORTING
8 = 3+1, 4+1 ADEMCO L/S EXPANDED
9 = 3+1, 4+1 RADIONICS EXPANDED
3