AQ2558P2X Installation Job Record

AQ25582B EXPANSION ZONING PANEL FOR 8 PUMPS
Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
customer.honeywell.com
® U.S. Registered Trademark
© 2013 Honeywell International Inc.
69-1980—05 L.L. Rev. 10-13
Printed in United States
C1 Zoning Module DIP Switch Settings
C2 Zoning Module DIP Switch Settings
* If used with AQ250 RelayPlus Control Panel, the AQ15000B Boiler Control
Module DIP switch #5 must be set to “GROUP” position and DIP switch #6 must
be set to “MAIN” position
If used with AQ251 Boiler Reset Control Panel, the EQUIPMENT SETUP >
AUXILIARY I/O > AUX PUMP menu option on the AQ251 must be set to
"GROUP"
DIP
Number
Description
1 Zone Address
(Slide the DIP switch to the right position to indicate which group of zones
this is; should be set to "1-4" for the first 4 space heating zones in the
system [usually included with an AQ250 or AQ251 control panel], then
"5-8" for the next group of 4 zones and so on. For each group of 4 zones,
there can be only one
DIP switch in the right hand position.)
2
3
4
5
If set to SYNC, zone synchronization is enabled.
If set to NOT, zone synchronization is disabled.
6
If zone valves are normally closed (N.C.), set the NC/NO DIP switch to
the OFF position.
If zone valves are normally open (N.O.), set the NC/NO DIP switch to
the ON position.
7
If set to Group (ON position) the zone outputs are energized with the
AUX pump*.
If set to - (OFF position), the AUX Pump contacts are not affected by
activity on these zones.
8
If set to 2-Stg (ON position), then 2-stage operation is activated on
thermostat inputs. The zoning module operates as two 2-stage zones
or 3 zones (one 2-stage and two 1-stage).
If set to 1-Stg (OFF position), then operates as four 1-stage zones.
M23715
Test
Diagnostic
Test
Diagnostic
Factory
Setting
Installer
Setting
Fill in the circle to
indicate position
of DIP switch.
M23720
A
AQ15540B
Test
Diagnostic
Test
M34972
ON
12345678
* If used with AQ250 RelayPlus Control Panel, the AQ15000B Boiler Control
Module DIP switch #5 must be set to “GROUP” position and DIP switch #6 must
be set to “MAIN” position
If used with AQ251 Boiler Reset Control Panel, the EQUIPMENT SETUP >
AUXILIARY I/O > AUX PUMP menu option on the AQ251 must be set to
"GROUP"
DIP
Number
Description
1 Zone Address
(Slide the DIP switch to the right position to indicate which group of zones
this is; should be set to "1-4" for the first 4 space heating zones in the
system [usually included with an AQ250 or AQ251 control panel], then
"5-8" for the next group of 4 zones and so on. For each group of 4 zones,
there can be only one
DIP switch in the right hand position.)
2
3
4
5
If set to SYNC, zone synchronization is enabled.
If set to NOT, zone synchronization is disabled.
6
If zone valves are normally closed (N.C.), set the NC/NO DIP switch to
the OFF position.
If zone valves are normally open (N.O.), set the NC/NO DIP switch to
the ON position.
7
If set to Group (ON position) the zone outputs are energized with the
AUX pump*.
If set to - (OFF position), the AUX Pump contacts are not affected by
activity on these zones.
8
If set to 2-Stg (ON position), then 2-stage operation is activated on
thermostat inputs. The zoning module operates as two 2-stage zones
or 3 zones (one 2-stage and two 1-stage).
If set to 1-Stg (OFF position), then operates as four 1-stage zones.
M23715
Test
Diagnostic
Test
Diagnostic
Installer
Setting
Fill in the circle to
indicate position
of DIP switch.
Factory
Setting
M23720A
AQ15540B
Test
Diagnostic
Test
M34972
ON
12345678