Specifications

Transformers
70-6910 177
Home
Controls Indoor Air Quality
Residential
Combustion Controls Hydronic Controls
Water
Controls Building Automation
Commercial
Components Pneumatic Controls
Industrial Combustion
Controls
AT88 Transformer
Powers 24 Vac air conditioning circuits and other applications that
do not exceed the listed ratings.
Meets NEC Class 2 not wet, Class 3 wet and U.L. 1585
requirements.
Overload protection provided.
Color-coded leadwires for primary connections.
Dimensions in inches (millimeters) Temperature Rating: -20 F to +105 F (-29 C to +41 C)
Frequency: 50 Hz; 60 Hz
Electrical Connections (main)
Primary: 12 in. leadwires
Secondary: 12 in. leadwires
Approvals:
Canadian Standards Association: Certified
Underwriters Laboratories, Inc. UL Component Recognized.
23/32
(19)
23/32
(19)
PRIMARY
LEADWIRES
(2,3 OR 4)
SECONDARY
LEADWIRES
M 994A
MOUNTING
SCREW
HOLES (4)
SIDE
BOTTOM
3/16
(5)
2-15/16
(75)
1-3/4
(45)
3-5/16 (84)
2-23/32
(69)
2-11/32
(60)
7/32
(6)
2-3/16
(56)
1-3/4
(45)
Product Number
Electrical Ratings
Mounting
Dimensions, Approximate
Includes
(Primary
Voltage)
(Secondary
Voltage) (Output) (inch) (mm)
AT88A1005 120 Vac 26.5 V.O.C. 24 Vac at 75 VA Foot-mounted 2 15/16 in. high x
2 3/16 in. wide x
3 5/16 in. deep
75 mm high
56 mm wide x
84 mm deep
Internally fused secondary for
overload protection.
* AT88A1021 208 Vac, 240 Vac 26.5 V.O.C. 24 Vac at 75 VA Foot-mounted 2 15/16 in. high x
2 3/16 in. wide x
3 5/16 in. deep
75 mm high
56 mm wide x
84 mm deep
Internally fused secondary for
overload protection.
AT88A1047 480 Vac 26.5 V.O.C. 24 Vac at 75 VA Foot-mounted 2 15/16 in. high x
2 3/16 in. wide x
3 5/16 in. deep
75 mm high
56 mm wide x
84 mm deep
Internally fused secondary for
overload protection.
* TRADELINE models • SUPER TRADELINE models