Product Overview

C6097 Gas/Air Pressure Switch
63-9340
May 2007
© 2007 Honeywell International Inc.
Replace time-consuming switch installations with new, reliable
Honeywell C6097 Gas/Air Pressure Switches. The cutting-
edge technology will save you time and money. And C6097
Pressure Switches also reduce your inventory, because they
can be used with older, stand-alone component valves as well
as newer valves, such as the Integrated Gas Valve Train (IVT).
SPECIFICATIONS
Models:
C6097A Pressure Switch:
Breaks a circuit when pressure falls to scale setting.
See Scale Range table.
C6097B Pressure Switch:
Breaks a circuit when pressure rises to scale setting.
See Scale Range table.
Minimum Ambient Temperature:
5° F (-15° C)
Maximum Ambient Temperature:
140° F (60° C)
Connections (Depending on Model):
1/4-18 NPT tapping for main or high-pressure connections.
1/8-27 NPT tapping for vent or low-pressure connection
(air only).
Flange mount for connection to Honeywell Integrated Valve
Trains (internal vent only, no external connections).
Scale Range:
0.4 to 5" wc (0.10 kPa to 1.25 kPa).
3 to 21" wc (0.75 kPa to 5.23 kPa).
12 to 60" wc (3.0 kPa to 15 kPa).
1.5 to 7" psi (10.3 kPa to 48 kPa).
Approvals:
Underwriters Laboratories: Listed.
Canadian Standards Association: Listed.
Factory Mutual: Approved.
Industrial Risk Insurers: Acceptable.
CSD-1AFB: Acceptable.
Accessories:
32003041-001 C6097
Cover for manual reset models.
32003040-001 C6097
Cover for recycle models.
32003039-001
Position indication Lamp Kit.
Automation and Control Solutions
In the U.S.:
Honeywell
1985 Douglas Drive North
Golden Valley, MN 55422-3992
In Canada:
Honeywell Limited
35 Dynamic Drive
Toronto, Ontario M1V 4Z9
www.honeywell.com
To Learn More
For more information please contact your Honeywell
Distributor. Or visit http://customer.honeywell.com.