Technical data
Gas type: natural gas, town gas, LPG (gaseous),
flue gas, biogas (max. 0.1%-by-vol. H
2
S) and air.
Max. inlet pressure p
max.
= withstand pressure,
see page6 (Type table).
Switching capacity:
U I (
cos φ = 1)
I (
cos φ = 0.6)
C6097
24 – 240 VAC max. 5 A max. 0.5 A
Storage temperature:
-4 to +104°F (-20 to +40°C).
Maximum medium and ambient temperatures:
-40 to +140°F (-40 to +60°C).
Long-term use in the upper ambient temperature
range accelerates the ageing of the elastomer ma-
terials and reduces the service life (please contact
manufacturer).
The set switching point may palpably change in me-
dia and ambient temperatures below -22°F (-30°C).
Storage temperature: -4 to +104°F (-20 to +40°C).
Diaphragm pressure switch, silicone-free.
Diaphragm: NBR.
Housing: glass fibre reinforced PBT plastic with
low gas release.
Lower housing section: AlSi 12.
Enclosure: IP65. Safety class: 1.
Cable diameter: AWG24 to AWG13
(0.02 to 0.07" (0.5 to 1.8mm)).
Line entrance: ½" NPT conduit.
Electrical connection type: screw terminals.
Max. tightening torque, see Technical Information
bulletin C6097.
Weight: 9.5 to 11.3 oz (270 to 320g).
Dimensions
1/2" NPT
2.76"
(70 mm)
0.43"
(11 mm)
3"
(76 mm)
Logistics
Transport
Protect the unit from external forces (blows, shocks,
vibration). On receipt of the product, check that the
delivery is complete, see page 1 (Part designa-
tions). Report any transport damage immediately.
Storage
Store the product in a dry and clean place.
Storage temperature: see page5 (Technical data).
Packaging
The packaging material is to be disposed of in ac-
cordance with local regulations.
Disposal
Components are to be disposed of separately in
accordance with local regulations.
Certification
Directive on the restriction of the use of haz-
ardous substances (RoHS) in China
Scan of the Disclosure Table China RoHS2– see
certificates at www.docuthek.com
FM approved
Factory Mutual Research Class: 3510 Flow and pres-
sure safety switches.
Designed for applications pursuant to NFPA 85 and
NFPA 86.
UL listed
UL 353 Limit control.
Underwriters Laboratories