Gas pressure switch C6097 Technical Information · GB 4 Edition 01.19 • Monitoring of gas and air pressures (positive, negative and differential pressures) • Switches with falling or rising pressure.
Contents Gas pressure switch C6097 . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 1 Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 1.1 Use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 1.1.
Application C6097 with CE approval. Hand wheel with mbar scale. M16 cable gland for electrical connection. C6097 with UL listing and FM approval. Hand wheel with "WC and mbar scale. 1/2" NPT conduit for electrical connection. C6097 can be supplied with lock-off function. 1 Application The pressure switch monitors extremely low pressure differentials and triggers switch-on, switch-off or switch-over operations if a set switching point is reached. The switching point can be adjusted using a hand wheel.
Application 1.1 Use 1.1.
Application 1.2 Application examples 1.2.3 Systems leak tightness check 1.2.1 Low gas pressure monitoring For monitoring the minimum gas inlet pressure 1.2.2 Differential pressure monitoring Electronic safety shut-off valve SAV with leak tightness check of downstream devices Differential pressure switch for monitoring air filters C6097 · Edition 01.
Application 1.2.4 Air line with minimum pressure and flow monitoring 1.2.5 Low and high gas pressure protection device PI PI PI PZL 1/min C6097 VAS..N VAS..
Certification 2 Certification 2.3 UL listed Certificates – see Docuthek. USA and Canada 2.1 EU certified UL 353 Limit control. – 2014/35/EU (LVD) – Low Voltage Directive – 2014/30/EU (EMC) – Electromagnetic Compatibility Directive – (EU) 2016/426 (GAR) – Gas Appliances Regulation – EN 13611:2015+AC:2016 – EN 1854:2010 2.2 FM approved Factory Mutual Research Class: 3510 Flow and pressure safety switches. Designed for applications pursuant to NFPA 85 and NFPA 86. www.approvalguide.
Function 3 Function FM approved and UL listed pressure switches Pressure switch C6097A switches with falling pressure, C6097B switches with rising pressure. Once the set switching point is reached, a micro switch is activated in the pressure switch which is designed as a change-over contact. Hand wheel NO 1/2" NPT Conduit NC COM The switching pressure is adjusted using a hand wheel. 4 CE approved pressure switches Hand wheel M16 x 1.5 NO NC 4 2 1 C6097 · Edition 01.
Function 3.2 Positive pressure measurement 3.4 Differential pressure measurement Positive pressure measurement is designed, for example, for checking the fan function or measuring the min./max. gas pressure. Differential pressure measurement is designed for safeguarding an air flow rate or for monitoring filters and fans, for example. 4 4 2 2 3 1 1 3 Gas, air, flue gas, biogas The positive pressure is measured in the lower diaphragm chamber, port 1 (or 2).
Function Increasing negative pressure Decreasing negative pressure -6 -5 -4 -3 -2 -1 Increasing pressure Decreasing pressure 0 1 2 3 4 5 6 Do not connect port 4 (or 3) to pipes carrying gas! For further information, see page 14 (Ports). C6097 · Edition 01.
Function 3.5 Connection diagram L1 0 2 NO 3 COM 1 NC 3.5.1 Blue pilot lamp for 230 V AC or 110/120 V AC 1 2 NC NO L1 L1 3 COM 11 NO NC NO 2 2 NC NO NO 3 3 COM COM 2 2 NO NO 11 NC NC N N N N Contacts 3 and 2 close when subject to increasing pressure. Contacts 1 and 3 close when subject to falling pressure. On pressure switches that switch with rising pressure: The contact switches from NC 1 to NO 2. On pressure switches that switch with falling pressure: The contact switches from NO 2 to NC 1.
Function 3.6 Wiring When using silicone tubes, only use silicone tubes which have been sufficiently cured. Vapours containing silicone can adversely affect the functioning of electrical contacts. In the case of low switching capacities, such as 24 V, 8 mA, for example, we recommend using an RC module (22 Ω, 1 μF) in air containing silicone or oil.
Project planning information 4 Project planning information 4.1 Installation Installation in the vertical or horizontal position, or sometimes upside down, preferably with vertical diaphragm. If installed in a vertical position, the switching point pS will correspond to the scale value SK set on the hand wheel. If installed in another position, the switching point pS will change and no longer correspond to the scale value SK set on the hand wheel. Switching point pS must be checked. ps = SK ps = SK + 0.
Project planning information 4.2 Ports Ports 3 and 4 are connected to the micro switch chamber. 4.2.1 CE certified pressure switches Pipes carrying gas must not be connected to port 3 or 4! 2 Rp ¼" The port that is best protected against soiling (dust/humidity) is to be left open for ventilation (positive pressure measurement) to the atmosphere.
Project planning information 4.2.2 UL, FM certified pressure switches 4 ¼" NPT IP 65 1 4 / " NPT 18 Positive pressure C6097 Connect 1 Free 4 Negative pressure C6097 Connect 4 Free 1 Differential pressure C6097 If port 4 is at the top, IP 65 will not be satisfied. Connect for the higher for the lower absolute absolute pressure pressure 1 4 Port 4 is connected to the micro switch chamber.
Project planning information 4.3 Resetting pressure switches with manual reset For details of the pressure differential between the switching pressure and possible reset, see page 22 (Adjusting range, switching hysteresis). Manual reset C6097A3012, C6097A3038, C6097A3095, C6097A3111 lock off if the pressure drops to the set switching point. For resetting, the pressure must have risen to at least the set switching point plus the pressure differential between the switching pressure and possible reset.
Accessories 5 Accessories 5.2 Connecting set 5.1 Fastening set with screws, U-shape bracket .95") 20 ") 9 (0.7 20 (0.79 ") 64 (2.52") 39 (1.53") 5,2 (0.2") 24 (0.94") 43 -0,3 (1.69") 4,20 +0,1 (0.17") 16 (0.63") 6 (0.24") 10 (0.4") 45 (1.77") 25 (0.98") 47,5 For monitoring a minimum and maximum inlet pressure with two pressure switches attached to one another. (1.8 7") 40 (1.57") 75 (2 M4 x 12 M4 x 10 Order No.: 32003043-003/U 1 2 2 1 3 4 2 1x 2x 5.
Accessories 5.4 Standard socket set 5.6 Pilot lamp set, red or blue For CE certified pressure switches Order No.: 32003053-003/U. Pilot lamp, red: 110/120 V AC, I = 1.2 mA, Order No.: 32003044-003/U. 230 V AC, I = 0.6 mA, Order No.: 32003046-003/U. Pilot lamp, blue: 110/120 V AC, I = 1.2 mA, Order No.: 32003045-003/U. 230 V AC, I = 0.6 mA, Order No.: 32003047-003/U. For FM, UL certified pressure switches Order No.: 32003054-003/U. 5.
Accessories 5.7 LED set, red/green 5.8 Cover for auto reset 24 V DC, I = 16 mA; 24 V AC, I = 8 mA, Order No.: 32003048-003/U. 110 – 230 V AC, Order No.: 32003049-003/U. 1 2 3 4 Order No.: 32003040-003/U 5.9 Cover for manual reset Order No.: 32003041-003/U C6097 · Edition 01.
Accessories 5.10 Weather protection cover When the DG is installed outdoors, the weather protection cover provides permanent protection against condensation and weathering of housing parts. The weather protection cover is made of 1 mm (0,04")thick stainless steel. Installation position: vertical with the cable gland pointing downwards. E A D C B F 2 M4 x 16 screws with 2 cap nuts. The enclosed filter pad is designed to protect the open ⅛" port from the ingress of dirt or insects.
Technical data 6 Technical data 6.1 General Gas type: natural gas, town gas, LPG (gaseous), flue gas, biogas (max. 0.1 %-by-vol. H2S) and air. Max. inlet pressure pmax. = withstand pressure, see page 22 (Adjusting range, switching hysteresis). Electrical connection type: screw terminals. Diaphragm pressure switch, silicone-free. Diaphragm: NBR. Housing: glass fibre reinforced PBT plastic with low gas release. Lower housing section: AlSi 12. Enclosure: IP 65, safety class: 1. Max.
Technical data 6.3 UL, FM certified pressure switches Switching capacity: U = 24 – 240 V AC, I = max. 5 A at cos ϕ = 1, I = max. 0.5 A at cos ϕ = 0.6. Maximum medium and ambient temperatures: -40 to +60°C (-40 to +140°F). Line entrance: ½" NPT conduit. Cable diameter: AWG 24 to AWG 13, 0.02 to 0.07" (0.5 to 1.8 mm). 6.4 Adjusting range, switching hysteresis 6.4.1 CE certified pressure switches Type Adjusting range* mbar C6097A4110 1 – 10 C6097A4210 2.
Technical data Adjusting range* "WC (mbar) Max. inlet pressure with without venting line psi (mbar) psi (mbar) 0.1 – 0.16 (0.25 – 0.4) 8.5 (600) 7 (480) – 8.5 (600) 7 (480) – 8.5 (600) 7 (480) 0.3 – 0.6 (0.75 – 1.5) 8.5 (600) 7 (480) 1.2 – 2 (3 – 5) 8.5 (600) 7 (480) Lock-off Type Mean switching differential at min. and max. setting "WC (mbar) C6097A3004 C6097A3012 C6097A3038 C6097A3053 C6097A3079 0.4 – 4 (1 – 10) 1 – 20 (2.5 – 50) 12 – 60 (30 – 150) 1 – 20 (2.
Technical data 6.5 Dimensions 13,1 (0.52") 70 (2.76") 30 (1.2") 64 (2.52") 17 (0.7") 36 (1.4 2") 50 (2") Rp 1/8 M16 x 1,5 28,5 (1.12") Rp 1/8 43 (1.7") 4 x ø 3,61) (ø 0.14") 10,5 (0.41") 76 (3") ø 4,2 (ø 0.17") Rp ¼ 2,5 (0.1") 6.5.1 EU certified pressure switches 13 (0.51") 30,5 (1.2") 1) Holes 10 mm (0.4") deep, for self-tapping screws. C6097 · Edition 01.
Technical data 6.5.2 UL, FM certified pressure switches 13,1 (0.52") 70 (2.76") 30 (1.2") / " NPT 4 x ø 3,61) (ø 0.14") 64 (2.52") ¼" NPT (1.4 2") 50 (2") 13 (0.51") 18 (0.7") 36 18 11 (0.43") 10,5 (0.41") 76 (3") ø 4,2 (ø 0.17") 43 (1.7") ½" NPT Conduit 1) Holes 10 mm (0.4") deep, for self-tapping screws. C6097 · Edition 01.
Maintenance cycles 6.6 Converting units 7 Maintenance cycles See www.adlatus.org At least once per annum, at least twice per annum for biogas. C6097 · Edition 01.
Feedback Finally, we are offering you the opportunity to assess this “Technical Information (TI)” and to give us your opinion, so that we can improve our documents further and suit them to your needs.