Submittal Sheet

Honeywell
C7027A,
C7035A,
C7044A
MINIPEEPER ULTRAVIOLET
FLAME DETECTOR
THE
C7027A,
C7035A,
AND
C7044A
DETECT ULTRAVIOLET
RADIATION EMITTED FROM ALL FLAMES. THEY ARE USED
WITH FLAME SAFEGUARD CONTROLS TO PROVIDE SUPER-
VISION FOR GAS, OIL, OR COMBINATION GAS-OIL
BURNERS.
q
C7027A
0
C7035A
0
C7044A
l The C7027A,
C7035A,
and
C7044A
are used with the
following:
-Flame Safeguard Programmers/
Amplifiers
R4126
and R4127lR7255B
R4140IR7249A
R4150IR7259A
R4795lR7290
-Flame Safeguard Primary Controls/
Amplifiers
R4075C,D,E/R7249A
R4136C,D/R7249A
dA690G
Protectorelay Primary Control
-R7023C
Flame Detector Relay.
l The C7044A is also used with the following 50’ Hz Flame
Safeguard Controls/ Amplifiers:
R434l
/R7323
R4343lR7323
R4344IR7323
l
The C7027A mounts on a 1
I2
in. sighting pipe by means of an
integral collar.
l
The C7035A mounts on a 1 in. sighting pipe by means of an
integral collar. A shield protects the sensing tube.
l
The C7035A meets outdoor raintight requirements of Under-
writers Laboratories Inc., NEMA 3, and NEMA 4.
l
The C7044A mounts with a simple, l-screw bracket. Sensing
tube enclosed in stainless steel housing.
l
The C7044A is suitable for side or end viewing.
l Compact size makes the C7027A and C7044A particularly
useful for blast tube mounting.
l Properly installed, the
C7027A
and
C7035A
are sealed
against pressures as high as 5 psi
134.5
kPa].
l
The C7035A ultraviolet sensing tube is field replaceable. The
C7027A and C7044A sensing tubes are not field
replaceable-
use on an economical, throwaway basis.
l
Two Minipeeper detectors can be wired in parallel for difficult
sighting applications.
I
SPEClFlCATlOhiS
I
STANDARD MODELS
C7035A MINIPEEPER ULTRAVIOLET FLAME DETECTOR
C7027A MINIPEEPER ULTRAVIOLET FLAME DETECTOR
DETECTION: Detects ultraviolet radiation only.
AMBIENT OPERATING TEMPERATURE RATINGS: 0 F to
+215
F
[-18 C to
+102
C], or -40 F to
+215
F r-40 C to
+102
C], depending
on the model.
MAXIMUM PRESSURE RATING: 5 psi
[34.5
kPa].
MOUNTING: Collar with standard
l/2
in. internal threads for
mounting on a
l/2
in. sighting pipe.
WIRING CONNECTIONS: Two, 6
ft
[1.83
m], color-coded, NEC Class
1 leadwires. (One model is available with 24
ft
[7.32
m] leadwires.)
Rear of detector has a clamp type connector for
l/2
in. flexible
metallic conduit. (Models are available with
l/2
in. internally
threaded spud connector instead of the clamp.)
DIMENSIONS: See Fig. 1.
REPLACEMENT PART: 129685 Flange Gasket NOTE: The UV
sensing tube is not field replaceable.
DETECTION: Detects ultraviolet radiation only.
AMBIENT OPERATING TEMPERATURE RATINGS: 0 F to 250 F
[-18 C to
+121
C], or -40 F to +250 F
[-40
C to
+121
Cl, depending
on the model.
MAXIMUM PRESSURE RATING: 5 psi
[34.5
kPa].
MOUNTING: Collarwith standard 1 in. internal threadsfor mounting
on a 1 in. sighting pipe. (The DIN approved C7035A1064 has l-1 1
BSRPl
threads.)
WIRING CONNECTIONS: Two, 6 ftt1.83 m], color-coded, NEC Class
1 leadwires. (One model is available with leadwires rated for
400 F
[204.4 C], and one model is available with 12
ft
[3.66
m]
leadwires.) Rear of detector has 112-14 NPSM internal
threads for connecting to a conduit. (The DIN approved
C7035A1064 has
l/2-14
BSP-F threads.)
DIMENSIONS: See Fig. 2.
WEIGHT: 6
oz
[0.17
kg].
REPLACEMENT PARTS:
129808 Flange Gasket.
129464M Ultraviolet Sensing Tube, 0 F to250 F
I-18
C to+121 C].
129464N Ultraviolet Sensing Tube, -40 F to
+250
F [-40 C to
+121
C].
C7027A AND C7035A
APPROVALS:
UNDERWRITERS LABORATORIES INC. LISTED: File No.
MP268; Guide No. MCCZ.
CANADIAN STANDARDS ASSOCIATION CERTIFIED: File No.
LR1620; Guide No. 140-A-2.
FACTORY MUTUAL APPROVED.
FIG. I- INSTALLATION DIMENSIONS OF THE
C7027A, IN in. [mm
DIN APPROVED MODELS:
C7027A1056,
C7035A1049,
and
IN BRACKETS]. C7035A1064.
D.A.
Form Number
65-0062
12-66e
cHoneywell Inc. 1986