THE FIRING LINE Honeywell Flame Sensors (Scanners) Cross Reference CROSS REFERENCE HONEYWELL FIREYE™ Visible Light 48PT1 C7003 Table 1 page 2 48PT2 C7010 Table 2 page 2 45AM1 C7013 C7014 Q174 45CM1 Table 3 page 3 1291 Table 18 page 16 Table 19 page 17 UV-7 C7915 page 4 Table 5 page 5 Ultraviolet C7012 page 6 Table 17 page 15 45UV2 PYRONICS 45UV3 4350 Table 19 page 17 45UV1 45UV5 Table 6 BARBER COLEMAN 1292 UV-6 Table 4 Table 18 page 16 UV-1 Q231 Q283 Table 16 page 14
Functions of Device to be Replaced a Device to be Replaced Current a Replacement Pipe Mounting Size NPT (in.) C7003A1005 None a 2 C7003A1013 None a 2 C7003A1021 None a 2 Used With All rectification type amplifiers and primaries. (Uses 38316 Photocell.) Comments Less finned casting and less removable glass window. International model. A possible solution would be to update to a 7800 Series replacement using the R7852B amplifier and the visible light detector C7962B. Table 2.
Table 3. C7013 AND C7014 RECTIFYING PHOTOCELL AND MOUNT CROSS REFERENCE (ALSO INCLUDES INFORMATION ON Q174 AND Q231) Specifications of Device to be Replaced Device to be Replaced Current a Replacement C7013A1003 None a Yes No No — C7013A1011 None a Yes No Yes — C7013A1029 None a Yes Yes No — C7014A1002 None a No No No — C7014A1010 None a No No No 6-32 NC screw instead of Rajah connector. Q174A1002 None a Yes No No Old OS number of C7013.
Specifications of Device to be Replaced Device to be Replaced Current Replacement a g Mounting Pipe Size NPT (in.) Lead Length (in.
Table 5. C7915 INFRARED FLAME DETECTOR CROSS REFERENCE. Specifications of Device to be Replaced Device to be Replaced Mounting Lead Current Pipe Size Length (in.) Replacement a NPT (in.) C7915A1002 Not Released 3/4 C7915A1010 C7915A1010 3/4 30 C7915A1028 C7915A1028 3/4 48 C7915A1036 C7915A1036 3/4 C7915A1044 C7915A1044 3/4 Orifice Collimating Lens d Cell Type Yes 1 Yes Yes 1 Requires Flame amplifier R7852. Yes Yes 1 With Heat Block and reducer bushing.
Specifications of Device to be Replaced Device to be Replaced Current Replacement Voltage/ Mounting Frequency Pipe Size HZ NPT (in.) Lead Length (ft./in.
Specifications of Device to be Replaced Device to be Replaced Current Replacement Voltage/ Mounting Frequency Pipe Size NPT (in.) HZ Lead Length (ft./in.) Ambient Temp ºF Solid State Shutter Comments C7012C1059 None 120/50,60 1 8/96 25 to 175 Yes No Explosion-proof housing. International model. C7012C1067 None 208/50,60 1 8/96 25 to 175 Yes No Explosion-proof housing. International model.
Device to be Replaced C7012E1252 Current Replacement Voltage/ Mounting Frequency Pipe Size NPT (in.) HZ Lead Length (ft./in.) Ambient Temp ºF Solid State Shutter Comments Not Released — C7012E1260 Not Released C7012E1278 C7012E1278 120/50,60 1 None -20 to 175 Yes Yes With Brad Harrison type connector — C7012F1003 C7012F1052 d 120/50,60 1 8/96 -20 to 125 No Yes Explosion-proof housing. C7012F1011 None 120/50,60 1 8/96 -20 to 125 No Yes Explosion-proof housing.
Specifications of Device to be Replaced Current Replacement Device to be Replaced Voltage/ Mounting Frequency Pipe Size NPT (in.) HZ Lead Length (ft./in.) Ambient Temp ºF Solid State Shutter Comments C7012X1084 None 120/50,60 3/4 8/96 h No Yes Self-check C7012X1092 C7012E1203 a 240/50,60 3/4 8/96 25 to 135 No Yes Fungus-proof C7012X1100 None 120/50,60 1 5/60 h No Yes Explosion-proof C7012X1118 None 220/50 3/4 8/96 h No Yes Self-check. International Model.
Specifications of Device to be Replaced Current Device to be Replaced Replacement Voltage (Vdc) Mounting Pipe Size NPT (in.) Lead Length (ft./in.) Ambient Temp ºF Solid State Shutter C7024E1001 C7024E1001 24 3/4 8/96 -40 to 175 Yes Yes C7024F1009 C7024E1001 24 1 8/96 -20 to 175 Yes Yes Comments Explosion-proof housing. Table 9. C7027 AND C7044 ULTRAVIOLET FLAME DETECTOR CROSS REFERENCE.
Table 10. C7035 ULTRAVIOLET FLAME DETECTOR CROSS REFERENCE. Specifications of Device to be Replaced Mounting UV Tube Pipe Size Current Device to be Replaced Replacement b Included a NPT (in.) C7035A1007 C7035A1023 129464M 1 Lead Length (ft./in.
Specifications of Device to be Replaced Device to be Replaced Current Replacement C7061A1004 C7061A1004 C7061A1012 C7061A1020 Voltage/ Frequency Hz Mounting Lead Pipe Size Length NPT (in.) (ft./in.
Table 14. C7076 ULTRAVIOLET FLAME DETECTOR CROSS REFERENCE. Specifications of Device to be Replaced Current Device to be Replacement a Replaced Voltage/ Frequency Hz Mounting Lead Pipe Size Length NPT (in.) (ft./in.
Specifications of Device to be Replaced Device to be Replaced Current Replacement a b Mounting Lead Pipe Size Length Collimating NPT (in.) (in.) Orifice Lens With Cell Comments FIREYE™ 48PT11000 C7915A1028 1/2 24 No No Yes With heat block, straight body. 48PT11003 C7915A1028 c 1/2 96 No No Yes With heat block, straight body. 48PT11007 C7915A1028 1/2 48 No No Yes With heat block, straight body. C7915A1028 d 1/2 24 No No Yes With heat block, angle body.
Table 17. FIREYE™ ULTRAVIOLET FLAME DETECTOR CROSS REFERENCE. Specifications of Device to be Replaced Device to be Replaced Current Replacement a Mounting Pipe Size NPT (in.) Lead Length (ft./in.) Ambient Temp ºF Comments FIREYE™ C7027A1080 b d 1/2 6/72 -40 to 212 Angle body. UV-1A3 C7027A1080 b 1/2 3/36 -40 to 212 Straight body. UV-1A6 C7027A1080 b 1/2 6/72 -40 to 212 Straight body. C7027A1080 b 3/8 3/36 -40 to 212 Straight body.
Specifications of Device to be Replaced Current Replacement Device to be Replaced Voltage/ Mounting Frequency Pipe Size HZ NPT (in.) Lead Length (ft./in.) Ambient Temp ºF Solid State Shutter Comments FIREYE™ 45UV11020 C7012A1152 b e 120/50,60 1 None 200 max. N/A 45UV11021 C7012A1152 b e 120/50,60 1 None 220 max. N/A 45UV51000 C7012E1112 b e 120/50,60 1 None 200 max. Yes 120/50,60 1 8/96 200 max.
Table 19. FIREYE ULTRAVIOLET FLAME DETECTOR CROSS REFERENCE. Specifications of Device to be Replaced Mounting Pipe Size NPT (in.) Lead Length (ft./in.) C7027A1080 b c 3/4 7 C7027A1031 b c 1 (NPS union) 1 1/2 Current Replacement a Device to be Replaced Ambient Temp ºF Comments Barber Coleman 1292 212 max. Straight body. Pyronics 4350 -40 to 212 Angle body. P-CI C7027A1080 b c Unknown 6 212 Angle body. P-CII C7027A1080 b c 3/4 NPS 6 212 Straight body.
THE FIRING LINE HONEYWELL FLAME SENSORS (SCANNERS) CROSS REFERENCE 70-8317—01 18
THE FIRING LINE HONEYWELL FLAME SENSORS (SCANNERS) CROSS REFERENCE 19 70-8317—01
THE FIRING LINE HONEYWELL FLAME SENSORS (SCANNERS) CROSS REFERENCE Automation and Control Solutions Honeywell International Inc. 1985 Douglas Drive North Golden Valley, MN 55422 Honeywell Limited-Honeywell Limitée 35 Dynamic Drive Toronto, Ontario M1V 4Z9 customer.honeywell.com ® U.S. Registered Trademark © 2010 Honeywell International Inc. 70-8317—01 M.S. Rev. 07-10 Printed in U.S.A.