Install Instructions

C7031G; C7041B,C,F,K; T775-SENS-OAT/STRAP SERIES 2000 ELECTRONIC TEMPERATURE SENSORS
3 62-0220—03
Immersion Well Mounting (C7031D, C7041D)
NOTE: The C7041D uses the 50001774-001 Well
Assembly. See Fig. 5 for dimensions.
The C7031D Sensor includes an immersion well. The
C7041D Sensor does not include a well. For the C7041D,
order the well as an accessory (part no.: 50001774-001).
When used on a boiler, follow the manufacturer
instructions for location. If a tapped hole is not provided
for the immersion well, provide one as follows:
1. Drain boiler and drill a 23/32 in. (18 mm) hole at the
selected location.
2. Cut threads in the hole with a 1/2 in. (13 mm) by
14 NPT tap.
In other installations, mount the immersion well in an
elbow with a heel outlet as shown in Fig. 3.
1. Drain the system, if you have not already done it,
and open the tapped hole.
2. Put pipe joint compound on the threads of the
immersion well and screw it into the tapped hole or
elbow, tightening it securely.
3. Refill the system and check for leaks.
Mount the C7031D/C7041D into the well:
NOTE: Mounting using previously installed
Honeywell wells (part no.: 32005960-001)
requires an adapter
(part no.: 50001775-001).
1. When an adapter is required, first thread it into the
well no more than one or two turns.
2. Slide the sensor into the well.
3. Rotate the sensor to thread it tightly into the adapter
and the adapter tightly into the well.
Fig. 3. Method of Mounting C7031D/C7041D Sensor.
Fig. 4. C7031D, C7041D Dimensions in in. (mm).
Fig. 5. 50001774-001 Immersion Well Dimensions in in. (mm).
1/2 NPT (13)
M22135
SENSING ELEMENT
(SEALED IN STAINLESS STEEL
TUBE INSIDE OF INSERTION WELL)
2-5/16
(59)
1-11/16
(43)
4-3/16
(107)
1/4
(6)
4
(70)
1-11/16
(43)
6-11/16 (170)
M22596
5 (127)
1/2 NPSM (13)
3/4 (19)
3/8
(10)
1 (26) 4 (102)
FITS 1/2 NPT TAPPED HOLE
M22597
1/2 NPSM
INTERNALLY
THREADED