User Guide

C7027A, C7035A, C7044A, C7927A MINIPEEPER
®
ULTRAVIOLET FLAME DETECTORS
60-2026—14 10
For the R7849A,B or R7851B Amplifiers used with the 7800
SERIES controls, a volt-ohmmeter with a zero to 5 or 10 Vdc
scale and a minimum sensitivity of one megohm/volt is
recommended, (see Fig. 11).
Fig. 11. Measuring flame signal voltage
of 7800 SERIES controls.
Measure the flame signal voltage as illustrated in Fig. 11 and
12. Be careful to connect the positive meter lead to the positive
(+) amplifier jack and the negative meter lead to the negative
(-) amplifier jack (BCS 7700) or the (-Com) jack for a 7800
SERIES control. If the BCS 7700 and Series 7800 controls
have the optional Keyboard Display Module, a zero to five Vdc
reading will be displayed on the module.
Move the flame detector and sight pipe (if not permanently
attached to the burner/boiler) to view the flame from various
positions. Allow a few seconds for the meter reading to
stabilize. A maximum steady microamp or voltage reading is
desirable. The flame signal must be above the minimum
acceptable level for the flame safeguard control and
associated amplifier as indicated in Table 1.
Measure the flame signal for the pilot alone, the main burner
flame alone, and both together (unless monitoring pilot only
when using an intermittent pilot or supervising the main flame
only when using direct spark ignition). Also, measure the flame
signal at low and high firing rates and while modulating (if
applicable).
With the flame detector in its final position, all flame signals
must be steady with a current/voltage value as indicated in
Table 1. If the minimum signal cannot be obtained or is
unstable, refer to Troubleshooting, page 12.
Pilot Turndown Test
If the detector is used to prove a pilot flame before the main
fuel valve can be opened, perform a Pilot Turndown Test.
Follow the procedures in both the Instructions for the
appropriate flame safeguard control, and in the burner
manufacturer's instructions.
Fig. 12. Measuring the BCS 7700 flame signal voltage.
NEGATIVE (-)
METER LEAD
POSITIVE (+)
METER LEAD
ONE
MEGOHM/VOLT
METER
M7382
RESET
BUTTO N
PRO G RAM
MODULE
20,000
VO LT-
OHMM
METER
PRO BES
FLAM E
AM PLIFER
BCS 7700 CHASSIS MODULE FOOTMOUNT
M7860