Submittal Sheet

PRODUCT DATA
® U.S. Registered Trademark
© 2004 Honeywell International Inc.
All Rights Reserved
60-2350—8
C7046A,B,C,D
Air Temperature Sensors
APPLICATION
The C7046 series of Air Temperature Sensors function as
primary and/or secondary sensors in electronic control
systems.
FEATURES
C7046A,C Sensors have probe lengths of 8 in.
(203 mm) and nominal sensor resistance of 3000 ohms
at 77°F (25°C).
C7046B Sensor has probe length of 6 in. (152 mm) and
nominal sensor resistance of 22,800 ohms at 77°F (25°C).
C7046D Sensor has probe length of 8 in. (203 mm) and
nominal sensor resistance of 1097 ohms at 77°F (25°C).
Carbon type, negative temperature coefficient
(NTC) thermistor sensing element in the C7046A,B,C
and platinum thin film, positive temperature coefficient
(PTC) element in C7046D precisely measures
temperature changes.
No settings or calibration required.
Solid state components not affected by dust or dirt.
Fast reacting.
Rugged stainless steel insertion probe.
Mounts on duct or plenum surface with mounting
flange or in a 2 in. by 4 in. (51 by 102 mm) junction box.
C7046B can be used as a replacement for C7100B
Averaging Temperature Sensor where duct or plenum
cross section is less than 13 in. (330 mm).
Contents
Application ........................................................................ 1
Features ........................................................................... 1
Specifications ................................................................... 2
Ordering Information ........................................................ 2
Installation ........................................................................ 3
Wiring ............................................................................... 4
Operation and Checkout .................................................. 5

Summary of content (8 pages)