User Guide

PRODUCT DATA
63-2140-09
C7400A and C7400C
Enthalpy Sensors
APPLICATION
The C7400A Enthalpy Sensor is used with the economizer
logic modules with the A,B,C, and D performance curves; the
C7400C sensor is used with the logic modules with the
A,B,C,D, and E performance curves. The sensors combined
with the economizer logic modules permit the use of outdoor
air as the first stage of cooling in heating, ventilating and air
conditioning (HVAC) systems.
FEATURES
Senses and combines temperature and humidity of
outdoor air.
As enthalpy of outdoor air increases, the outdoor air
damper closes to a preset minimum position.
As enthalpy of outdoor air becomes low, the outdoor
air damper opens to reduce the mechanical cooling
load in the building.
Maximum economizer savings is achieved when two
C7400 Enthalpy Sensors are used for differential
enthalpy changeover control.
Compact size and lightweight construction allows
easy mounting in HVAC rooftop unit. A duct mounting
kit
a
is available for the 2000 series sensor models
(C7400A2xxx and C7400C2xxx).
Sensors are enclosed in a rugged, corrosion-resistant
glass-fiber reinforced plastic duct-mount case.
Provides a 4 to 20 mA output signal to Economizer
Logic Module; setpoint is located on the logic module.
a
Honeywell part number 50053060-001
Contents
Application ........................................................................ 1
Specifications ................................................................... 2
Installation ........................................................................ 2
Ordering Information ........................................................ 2
Operation .......................................................................... 4

Summary of content (8 pages)