Submittal Sheet

CURRENT SWITCHES SPLIT AND SOLID CORE
3 31-00145—02
White Boxes: Sensor response time at specified current levels above each models fixed trip point.
Gray Boxes: Sensor response time at specified current levels less than or equal to each models fixed trip point.
Each sensor should be tripped by the time it reaches the fixed trip point for that model.
REGULATORY INFORMATION
FCC REGULATIONS: § 15.19 (A)(3)
This device complies with part 15 of the FCC Rules.
Operation is subject to the following two conditions:
1. This device may not cause harmful interference, and
2. This device must accept any interference received,
including interference that may cause undesired
operation.
IC REGULATIONS: RSS-GEN
This device complies with Industry Canada’s license-
exempt RSSs.
Operation is subject to the following two conditions:
1. This device may not cause interference; and
2. This device must accept any interference, including
interference that may cause undesired operation of
the device.
Le présent appareil est conforme aux CNR d’Industrie
Canada applicables aux appareils radio exempts de
licence. Lexploitation est autorisée aux deux conditions
suivantes :
1. l’appareil ne doit pas produire de brouillage;
2. l’utilisateur de l’appareil doit accepter tout brouil-
lage radioélectrique subi, même si le brouillage est
susceptible d’en compromettre le fonctionnement.
FCC WARNING (PART 15.21) (USA ONLY)
Changes or modifications not expressly approved by the
party responsible for compliance could void the users
authority to operate the equipment.
Table 1. Standard Ordering.
Model #
Trip Point
Type
Normally
(Open/Closed)
Core
(Solid/Split) Amp Range Trip Point Contact Rating
CS-O-A
Adjustable
Open Solid
0 to 250 A
0.5 to 220 A
0.2 A @ 200 VAC/VDC
CP-O-A Open Split 1.5 to 220 A
CP-O-AL Open Split 0.6 to 180 A
CP-C-A Closed Split 1.5 to 220 A
CS-O-F
Fixed
Open Solid 0.25 A or less
CS-C-F Closed Solid 0.25 A or less
CP-O-F Open Split 1.5 A or less
CP-O-FL Open Split 0.5 A or less
CP-C-F Closed Split 1.5 A or less
Table 2. Response Time — Adjustable Trip Point Models.
Model # 0.50 Amps 0.60 Amps 0.75 Amps 1.0 Amps 1.5 Amps 10 Amps 20 Amps
CS-O-A 221 mS --- 144 mS 109 mS ---
63 mS 59 mS
CP-O-A --- --- --- --- 248 mS 68 mS 65 mS
CP-O-AL --- --- --- --- 344 mS 92 mS 86 mS
CP-C-A --- 400 mS 270 mS 183 mS --- 62 mS 60 mS
Table 3. Response Time — Fixed Trip Point Models.
Model #
0.15
Amps
0.20
Amps
0.25
Amps
0.50
Amps
0.75
Amps
1.0
Amps
1.20
Amps
1.50
Amps
10
Amps
20
Amps
CS-O-F
156 mS 100 mS 84 mS --- --- 32 mS --- --- 26 mS 24 mS
CS-C-F
--- 189 mS 134 mS --- --- 48 mS --- --- 42 mS 41 mS
CP-O-F
--- --- --- 484 mS 72 mS --- 45 mS 26 mS 20 mS
CP-O-FL --- --- --- --- --- --- 194 mS 102 mS 42 mS 42 mS
CP-C-F
--- 224 mS 144 mS 65 mS 47 mS 39 mS --- --- 25 mS 22 mS