Specification Sheet

51-52-03-36
Page 10
Table 1—Input Actuations
Range
Input 1 Actuation °F °C
Thermocouples
(Per ITS-90)
B
E
E (low)
J
J (med)
J (low)
K
K (med)
K (low)
NiMo-NiCo (NNM90)
NiMo-NiCo (low)
Nicrosil-Nisil (NIC)
NIC (low)
R
S
T
T (low)
W5W26
W5W26 (low)
PR40-PR20
0 to 3300
–454 to 1832
–200 to 1100
0 to 1600
20 to 900
20 to 550
0 to 2400
–20 to 1200
–20 to 750
32 to 2500
32 to 1260
0 to 2372
0 to 1472
0 to 3100
0 to 3100
–300 to 700
–200 to 500
0 to 4200
0 to 2240
32 to 3416
–18 to 1816
–270 to 1000
–129 to 593
–18 to 871
–7 to 482
–7 to 288
–18 to 1316
–29 to 649
–29 to 399
0 to 1371
0 to 682
–18 to 1300
–18 to 800
–18 to 1704
–18 to 1704
–184 to 371
–129 to 260
–18 to 2315
–18 to 1227
0 to 1880
Honeywell Radiamatic
Type RH
Type RI
0 to 3400
0 to 9999 max.*
–18 to 1871
–18 to 9999 max.*
Differential Thermocouple **
–50 to 150 –46 to 66
*User enters the range manually per RI type and application.
** Factory calibrated for pair of J thermocouples at an ambient temperature
mean of 450°F / 232°C. Can be Field Calibrated for other ambient
temperatures or other Thermocouple types.
Range
Input 1 Actuation °F °C
RTD
Per IEC-60751 (1995)
IEC Alpha = 0.00385
100 ohms
100 ohms (low)
200 ohms
500 ohms
–300 to 1200
–300 to 300
–300 to 1200
–300 to 1200
–184 to 649
–184 to 149
–184 to 649
–184 to 649
Linear
Milliamps
Millivolts
Volts
4 to 20 mA ***
0 to 20 mA ***
0 to 10 mV
0 to 50 mV
0 to 100 mV
1 to 5 V
0 to 5 V
0 to 10V ***
Input 2 Actuation
Milliamps
Volts
4 to 20 mA ****
0 to 20 mA ****
1 to 5 V
0 to 5 V
0 to 2 V
*** Requires external dropping resistor assembly (Honeywell supplied).
**** Input 2 has an internal dropping resistor for milliamp inputs.
General Reference Data
Isolation
(Functional)
Analog Inputs : are isolated from all other circuits at 850Vdc for 2 seconds, but not from each other.
Analog Outputs : are isolated from all other circuits at 850Vdc for 2 seconds.
AC Power : is electrically isolated from all other inputs and outputs to withstand a HIPOT potential of
1900Vdc for 2 seconds per Annex K of EN61010-1.
Relay Contacts : with a working voltage of 115/230 Vac, are isolated from each other and all other circuits
at 345Vdc for 2 seconds.
Surge Withstand
Capability (SWC)
Immunity: ANSI/IEEE C37.90.1, Surge Withstand Capability (SWC) (Formerly IEEE 472). Mains power
input and relay contact outputs: 2.5 kV, Common Mode and Differential Mode. All other circuits: 1.0 kV,
Common Mode and Differential Mode. The instrument is capable of meeting these test levels with no
component failures, no reset, and no incorrect outputs.
Radio Frequency
Interference
(RFI)
Immunity: No effect on performance from a 5 W walkie-talkie operated at 27, 151 or 450 MHz, one meter
from the controller.