Specifications
Design
CE Conformity (Europe) This product is in conformity with the protection requirements of the following European
Council Directives: 73/23/EEC, the Low Voltage Directive, and 89/336/EEC, the EMC
Directive. Conformity of this product with any other “CE Mark” Directive(s) shall not be
assumed.
Product Classification Class I: Permanently Connected, Panel Mounted Industrial Control Equipment with
protective earthing (grounding).
Enclosure Rating Panel Mounted Equipment: This controller must be panel mounted. Terminals must be
within the panel enclosure.
Front Bezel: NEMA3R and IP54, or NEMA4X and IP66 with 4 screws
Installation Category
(Overvoltage Category)
Category II: Energy-consuming equipment supplied from the fixed installation.
Local level appliances, and Industrial Control Equipment.
Pollution Degree Pollution Degree 2: Normally non-conductive pollution with occasional conductivity
caused by condensation. (Ref. IEC 664-1)
EMC Classification Group 1, Class A, ISM Equipment (EN 55011, emissions), Industrial Equipment
(EN61326, immunity)
Method of EMC Assessment Technical File (TF)
Declaration of Conformity
51453655
Approval Body Ratings UL Listed (Standard): UL61010C-1 (UL File# E201698)
CSA Certified (Optional): CSA1010-1
FM Approval for Limit Controller Model (Optional): Class Number 3545
Analog Inputs (One or Two)
(See Table 1 for Input
Actuations)
Accuracy:
± 0.25% of full scale typical (± 1 digit for display)
Can be field calibrated to ± 0.05% of full scale typical
16-bit resolution typical
Sampling Rate: Both inputs are sampled six times per second
Temperature Stability: ± 0.01% of Full Scale span / ˚C change—typical
Input Impedance:
4-20 Milliampere Input: 250 ohms
0-10 Volt Input: 200K ohms
All Other: 10 megohms
Maximum Lead Wire Resistance:
Thermocouples: 50 ohms/leg
100 ohm, 200 ohm and 500 ohm RTD: 100 ohms/leg
100 ohm Low RTD: 10 ohms/leg
Analog Input Signal Failure
Operation
Burnout Selections: Upscale, Downscale, Failsafe or None
Thermocouple Health: Good, Failing, Failure Imminent or Failed
Failsafe Output Level: Configurable 0-100% of Output range
Analog Input Filter
Software: Single pole lowpass section with selectable time constants, off to 120
seconds, available on both analog inputs.
Stray Rejection Common Mode
AC (50 or 60 Hz): 120 dB (with maximum source impedance of 100 ohms) or ±1 LSB
(least significant bit) whichever is greater with line voltage applied.
DC: 120 dB (with maximum source impedance of 100 ohms) or a ±1 LSB whichever is
greater with 120 Vdc applied.
DC (to 1 KHz): 80 dB (with maximum source of impedance of 100 ohms) or ±1 LSB
whichever is greater with 50 Vac applied.
Normal Mode