Submittal Sheet

PRODUCT DATA
63-2237-2
® U.S. Registered Trademark
Copyright © 2004 Honeywell International Inc.
All Rights Reserved
DM7600A, DM7600B
Commercial Zone Damper/Actuator
APPLICATION
The DM7600 Commercial Zone Damper/Actuator consists of
either an ML7161A (DM7600A) or an ML6161A (DM7600B)
Direct Coupled Actuator (DCA) assembled to a round duct
damper section (6 to 16 inches in diameter).
The DM7600 is intended to be used in commercial zoning
systems as an individual zone damper controlled by a zone
thermostat, and as a bypass damper controlled by a duct
static pressure sensor/controller.
A commercial zoning system controls discharge of a constant
volume HVAC unit with a series of zone dampers and a
bypass damper to provide the required space temperature by
varying both the delivered air temperature and volume. The
zone space thermostat positions the corresponding DM7600
to satisfy the space requirements.
DM7600B models with 7-minute actuators were specifically
designed for use with the T641 Floating Control Thermostat
and can be used for individual room zoning, etc.
FEATURES
Six damper sizes, 6 to 16 inches, in 2 inch increments.
One or two accessory switches available, adjustable
over 90° stroke.
Three inputs available: floating, 2-10 Vdc, 4-20 mA.
Same accessories and features available as for
ML6161 or ML7161.
SPECIFICATIONS
Models:
Actuators are 35 lb-in. torque, 90 second or 7 minute timing,
which control 90° dampers. Six damper sizes ranging from
6 to 16 inches (in two inch increments) are available. See
Table 1.
Table 1. DM7600 Models.
OS Number Actuator Damper Size (in.)
DM7600A1005 ML7161A2008 6
DM7600A1013 8
DM7600A1021 10
DM7600A1039 12
DM7600A1047 14
DM7600A1054 16
DM7600B1004 ML6161A2009 6
DM7600B1012 8
DM7600B1020 10
DM7600B1038 12
DM7600B1046 14
DM7600B1053 16
DM7600B1061 ML6161A2017 6
DM7600B1079 8
DM7600B1087 10
DM7600B1095 12
DM7600B1103 14
DM7600B1111 16