user manual

Input and Output Calibration for Recorder with Display
12/03 DR4300 Circular Chart Recorder Product Manual 155
Step Description Press Action/Result
4
Exit Calibration Mode
FUNC
The recorder stores the span value.
Repeat procedure for the other pen. Remove power from
recorder and disconnect the milliammeter and connect
output wiring.
DISP
or
SET
UP
To exit the calibration mode.