Air Cleaner Manual

F116 SERIES 2 SELF-CONTAINED DUCTABLE COMMERCIAL AIR CLEANER
68-0200-4 Revised 01/2010 10
INSTALLATION
WARNING
Explosion Hazard Possible.
Can cause personal injury or equipment damage.
Do not install or use the F116 Series 2 air cleaner
where there is any danger of gas, vapor or dust
explosion.
IMPORTANT
This air cleaner has not been investigated for use in
the ceilings of fire-resistant assemblies.
CAUTION
Electrical Hazard.
Can cause personal injury or equipment damage.
Turn off power before installing or servicing the air
cleaner.
IMPORTANT
Stand on a stable platform when working with the air
cleaner.
When Installing this Product…
1. Read these instructions carefully. Failure to follow them
could damage the product or cause a hazardous condi-
tion.
2. Check the ratings given in the instructions and on the
product to make sure the product is suitable for your
application.
3. Installer must be a trained, experienced service techni-
cian.
4. After installation is complete, check out product opera-
tion as provided in these instructions.
WARNING
Remove packing materials / Parts from inside the
Motor / Blower compartment prior to installation or
initial power on.
Mount Air Cleaner Cabinet
The F116 Series 2 air cleaner must be attached to a structure
capable of supporting the weight of the unit with filters, ducting
and plenums when used. Roof trusses, bar joists and floor
joists are examples of suitable structures.
MPORTANT
All suspension points (either six or eight depending
on the model) must be used for proper and safe
installation. See Fig. 1 and 2 for dimensions between
the suspension points.
Threaded rod, eyebolts with chains, or any standard practice
and hardware for hanging method can be used in the
suspension of the air cleaner. See Fig. 12.
NOTE: State and local codes and accepted installation prac-
tices must be followed.
Fig. 12. Fastening air cleaner to a structural support
system (bar joist, concrete slab, or timber framing).
Installation with Ducting
Use a transition or box plenum to attach the ducting to the air
cleaner inlet and outlet. On the inlet, a transition plenum is
preferred, see Fig. 13.
Fig. 13. Transition plenum connected to the air cleaner
inlet.
If a box plenum is used on the inlet, a diffusion screen must be
installed in the box, see Fig. 14. A box plenum can
accomodate more than one inlet
THREADED 
ROD
HEX BOLT
LOCK 
WASHER
TOP OF 
AIR CLEANER
CABINET
JAM
NUT
JAM NUT
3/8 x 16T
EYEBOLT
CHAIN
3/8 x 16T NUTS INSTALLED
IN CABINET CORNERS
FASTEN SECURELY TO STRUCTURAL SUPPORT SYSTEM
I.E. BAR JOIST, CONCRETE SLAB, TIMBER FRAMING, ETC.
ALL EXTERNAL HARDWARE
FURNISHED BY OWNER.
M10802
M7793A
AIR CLEANER