Air Cleaner Manual

F116 SERIES 2 SELF-CONTAINED DUCTABLE COMMERCIAL AIR CLEANER
68-0200-4 Revised 01/2010 14
Table 4. Troobleshooting the F116 Series 2 Air Cleaner
PARTS LIST
Refer to Fig. 18 and Table 5 for replacement part information
Model* Electrical Ratings
Motor will not start
Check wiring for loose connections - Tighten if neccessary.
Check capacitor - Replace if necessary.
Check for hot motor - Thermal protection relay is tripped, reset it.
•Replace motor.
Vibration - High Frequency Check that blower wheel is balanced - remove and balance or
replace wheel.
Vibration - Low Frequency Check if system is operating above 2.0” W.G. pressure - reduce
total pressure by replacing filters.
Scraping noise Check if the blower wheel is touching the blower housing - adjust
blower and position wheel in the center of the inlet ring.
Squeal or whistle noise Check for air leaks in the cabinet doors or ducting - plug air leaks.
Table 5. Replacement Parts.
Fig.
Reference No. Description Pack Qty Order Number Reference No.
1 Prefilter 1 box of 6 32000200 860039
2
99.97% HEPA media filter 1 32000198 860023
95% D.O.P hospital grade filter 1 32000195 860024
95% ASHRAE particle filter 1 32000196 860025
CPZ™ sorbent module (requires 2) 1 32004078-001 N/A
Charcoal sorbent module (requires 2) 1 32004078-002 N/A
Zeolite sorbent module (requires 2) 1 32004078-003 N/A
Permanganate sorbent module (requires 2) 1 32004078-004 N/A
OPTIONAL Parts not shown in Fig. 9.
Remote Wall 3-Speed Switch, Series 3 1 190097C
Capacitor, Series 2 1 32000551-001
Motor / Blower; 120 V, 60 Hz, Series 1 1 32000552-001
Motor / Blower; 208/230V, 50/60 Hz, Series 1 1 32000552-002
Motor / Blower; 120 V, 60 Hz, Series 2 1 32000552-003
Motor / Blower; 230V, 50 Hz, Series 2 1 32000552-004
Motor with Capacitor ; 120 VAC, 60Hz, Series 1 1 32000553-001
Motor with Capacitor; 230 VAC, 50Hz, Series 1 1 32000553-002
Motor; Three Speed120 VAC, 60Hz, Series 2 1 32000553-003
Motor; 230 VAC, 50Hz, Series 2 1 32000553-004