Application Considerations
The Honeywell Media Air Cleaner is designed to work with gas, oil, and electric forced warm air furnaces and with
compressorcooling.Itcanalsobeusedwithheatpumpsifthelterischangedregularlytopreventexcessive
pressure drop. The Honeywell Media Air Cleaner is not recommended for applications where pressure drop may
be critical.
Models
F100FMediaAirCleanerincludescabinet,accessdoorandMERV11pleatedmedialter.
F200FMediaAirCleanerincludescabinet,accessdoorandMERV13pleatedmedialter.
F100B Media Air Cleaner Boot includes cabinet and access door. (No Filter)
Air Conditioning
Mountthemediaaircleanerupstreamoftheevaporatorcoilinacoolingsystem.Thelterwillhelptokeepthecoil
clean and reduce maintenance.
Humidiers
Themediaaircleaneriscompatiblewithhumidiers.Avoidapplicationswherewatermistwillreachthemedia.If
anatomizing(steam)humidierisused,theltermediawillrequirereplacementmoreoftenbecauseofminerals
in the water.
UV Lights
GermicidalUVlightscancausedegradationofthemedialter.TheUVlightshouldbelocatedoutoflineofsight
oraminimumof3feetfromthelter.Otherwisetheltermayneedtobereplacedmorefrequently.