Installation Manual

411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D 13
Controls and Indicators
1.4 Controls and Indicators
Front Panel Switch
Reset Switch - to reset 411UDAC circuits
Acknowledge/System Silence Switch
press once to acknowledge alarm or trouble (silence local 411UDAC piezo sounder and change all
flashing LEDs to steady on)
press a second time and hold for minimum of two seconds to perform a System Signal Silence (silence
Notification Appliance Circuit)
411UDAC Piezo Sounder
The 411UDAC piezo sounder is used to locally annunciate DACT alarms and troubles. DACT troubles
include input channel open circuit, NAC fault, phone line 1 or 2 voltage fault, phone number 1 or 2
communication fault and total communication failure. Separate and distinct sounds are provided for the
following conditions:
alarm - steady On
trouble - 1 second On and 1 second Off
supervisory - ½ second On and ½ second Off
Front Panel Indicator
AC Power - green LED
Input Active - green LED
Communication Fail - yellow LED
System Trouble - yellow LED
Supervisory - yellow LED
Battery Trouble - yellow LED
Circuit Board Indicator
Earth Fault - yellow LED (indicates zero impedance between panel and earth ground)
FIGURE 1-3:411UDAC Controls and Indicators