Installation Manual

Program Mode
44
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D
Ademco Contact ID Format Secondary Central Station Event Codes
If ā€˜Eā€™ is entered for address 50, the following data is automatically programmed for the Secondary Central Station
phone number event codes. Enter '000' for the Setting to disable the report to the Central Station.
TABLE 3-4: Ademco Contact ID Format - Secondary
Address Description Setting
Channel/
Input #
233 - 235 Secondary # Input Channel 1 Active Event Code 111 001
236 - 238 Secondary # Input Channel 2 Active Event Code 115 002
239 - 241 Secondary # Input Channel 3 Active Event Code 111 003
242 - 244 Secondary # Input Channel 4 Active Event Code 115 004
245 - 247 Secondary # Input Channel 1 Fault Event Code 380 001
248 - 250 Secondary # Input Channel 2 Fault Event Code 380 002
251 - 253 Secondary # Input Channel 3 Fault Event Code 380 003
254 - 256 Secondary # Input Channel 4 Fault Event Code 380 004
257 - 259 Secondary # AC Voltage Fault Event Code 301 000
260 - 262 Secondary # Earth Fault Event Code 310 000
263 - 265 Secondary # Low Battery Fault Event Code 302 000
266 - 268 Secondary # No Battery Fault Event Code 311 000
269 - 271 Secondary # Phone Line 1 Voltage Fault Event Code 351 000
272 - 274 Secondary # Phone Line 2 Voltage Fault Event Code 352 000
275 - 277 Secondary # NAC Fault Event Code 321 000
278 - 280 Secondary # Charger Fault Event Code 300 000
281 - 283 Secondary # Phone Number 1 Communication Fault Event Code 354 001
284 - 286 Secondary # Phone Number 2 Communication Fault Event Code 354 002
287 - 289 Secondary # System Off Normal Fault Event Code 308 000
290 - 292 Secondary # System Test Message 602 000
293 - 295 Secondary # System Abnormal Test Message 608 000
296 - 298 Secondary # Upload/Download Request Code 411 000
299 - 301 Secondary # Upload Successful Code 416 000
302 - 304 Secondary # Download Successful Code 412 000
305 - 307 Secondary # Upload/Download Failed Code 413 000