Installation Manual

411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D 47
Program Mode
Secondary Central Station Number Account Code (51 - 54)
The four locations at addresses 51 - 54 default to all '0's. Valid entries are 0 - 9 and A - F. The number of digits
entered must match the format selection. If programming '2, 3, 4 or 5' into address 50, enter three digits (one digit
each in locations 51, 52 and 53 - location 54 is ignored). If programming '0, 1, 6, 7, 8, 9, A, B, C, D or E' into
address 50, enter four digits (one each in locations 51, 52, 53 and 54).
Secondary Central Station Number 24 Hour Test Time (55 - 58)
Use military time when entering the 24 hour 'test' time. The 24 hour test report to phone number 1 takes up four
locations, from addresses 55 - 58. The default is 00:00 (12:00 midnight). The limits for each location are as fol-
lows (do not use values of A - F as entries):
55: enter 0, 1 or 2
56: enter 0 - 9
57: enter 0 - 5
58: enter 0 - 9
Secondary Central Station Number 24/12/8/6 Hour Test Time Interval (59)
The test report sent to the Secondary phone number may be sent every 6, 8, 12 or 24 hours. If the message is to be
sent every 24 hours, leave the factory default entry of '0'. If other test report times are needed, enter 1 = 12 hour,
2 = 8 hour or 3 = 6 hour.
AC Loss Reporting Delay (60)
Enter a digit of 0 - 9 or A - F corresponding to the number of hours to be delayed in reporting the loss of AC
power. The factory default is '2' for 2 hours. The valid entries are '0' = no delay; '1' = 1 hours; '2' = 2 hours;
'3' = 6 hours; '4' = 7 hours; '5' = 8 hours; '6' = 9 hours; '7' = 10 hours; '8' = 11 hours; '9' = 12 hours; 'A' = 13 hours;
'B' = 14 hours; 'C' = 15 hours; 'D' = 16 hours; 'E' = 17 hours; 'F' = 18 hours.
Note: UL requires a minimum of 2 hours delay.
Backup Reporting (61)
Leaving address 61 at '0' means that reports will be transmitted to the secondary Central Station phone number
only if attempts to communicate to the primary Central Station phone number are unsuccessful. Programming a
'1' causes all reports to be transmitted to both the primary and secondary Central Station phone numbers. Pro-
gramming a '2' causes reports to go to the first available receiver.
CAUTION: Do not alter this entry while the digital communicator is active.
Reserved for Future Use (62)
DACT Trouble Reminder (63)
The factory default entry of '0' in address location 63 disables the trouble reminder feature. Selecting '1' for loca-
tion 63 will cause a reminding beep (after the Silence switch is pressed) every 15 seconds for active alarms and
every two minutes during a DACT trouble condition. The beeps from the onboard piezo sounder will occur until
the alarm or DACT fault is cleared. The piezo sounder will begin beeping at a rate of one second On and one
second Off after 24 hours unless the DACT fault has been cleared.
Operational Mode Selection (64)
The factory default setting is ‘0’ for latching inputs and the onboard communicator disabled. This prevents the
unit from transmitting status information to the Central Station(s).
TABLE 3-7: 411UDAC Operational Modes
Address 64 Setting 411UDAC Operational Mode 411UDAC Function
0 Stand-alone/Communicator Disabled latching inputs/onboard communicator disabled
1 Stand-alone/Communicator Enabled latching inputs/onboard communicator enabled
2 Slave/Communicator Enabled nonlatching inputs/onboard communicator enabled
3 Slave/Communicator Disabled nonlatching inputs/onboard communicator disabled
!