Central Station Communications
4.0.2 Ademco Contact ID Format Event Code Description
This section describes the various Event Codes and their messages which are available for the Ademco Contact ID
Format. The reporting structure for the Ademco Contact ID Format is as follows:
SSSS 18 QXYZ GG CCC
Where:
SSSS = Four digit Subscriber ID Account Code (addresses 21 - 24 and 51 - 54)
18 = Identifies transmission as Contact ID to the receiver at the Central Station
Q = Event Qualifier where 1 = New Event and 3 = New Restore
XYZ = Event code (shown in Tables)
GG = Group number
CCC = Channel/Input number
Notes:
1. 18, which is used in the reporting structure to identify the transmission as Contact ID, is not printed out in the
alarm and trouble report.
2. Q, which is the Event Qualifier for the reporting structure, is printed out in the report as an E for New Event or
R
for New Restore.
3. GG Group Number is fixed at '00' and cannot be changed.
4. CCC Channel/Input Number is transmitted as '001' for Channel/Input 1, '002' for Channel/Input 2, '003' for
Channel/Input 3, '004' for Channel/Input 4.
Ademco Contact ID Reporting Structure
A typical printout from a Central Station receiver (such as the Ademco 685) of alarm and trouble reports in the
Ademco Contact ID Reporting Structure follows:
Time
Date Rcvr/Line ID SSSS QXYZ GG CCCC
11:28 03/25 11 7777 E110 00 C001 - general fire alarm on Channel/Input 1
11:28 03/25 11 7777 E111 00 C002 - smoke detector alarm on Channel/Input 2
11:28 03/25 11 7777 E380 00 C003 - fault on Channel/Input 3
11:28 03/25 11 7777 R110 00 C001 - Channel/Input 1 alarm restored
11:28 03/25 11 7777 R111 00 C002 - smoke detector Channel/Input 2 restored
11:28 03/25 11 7777 R380 00 C003 - Channel/Input 3 fault restored
11:28 03/25 11 7777 E158 00 C004 - high temperature, Channel/Input 4
11:28 03/25 11 7777 E151 00 C004 - gas detected, Channel/Input 4