Installation Manual

411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D 65
Battery Calculations
CHAPTER 6 Battery Calculations
Use the Total Standby and Alarm Load Currents calculated in Table 6-2, “Load in Standby,” on page 66, and Table 6-
3, “Load in Alarm,” on page 66, for the following battery calculations.
1. Select a battery with an Amp Hour rating greater than that calculated in Table 6-1 .
NFPA 72 for Central Station and Proprietary Protected Premises systems require 24 hours of standby
NFPA 72 for Auxiliary and Remote Station systems require 60 hours of standby (14 Amp Hours)
2. Two 12 VDC, 7 Amp Hour batteries, wired in parallel, can be located in the backbox to provide 14 Amp
Hours of backup (refer to Figure 2-5 on page 22 for battery cable connections)
TABLE 6-1: Battery Calculations
Standby Load
Current in amps
(from Table 6-2 )
[ ]
X
Required Standby Time in Hours
(24 or 60 Hours)
[ ]
= __________
Alarm Load
Current in amps
(from Table 6-3 )
[ ]
X
Required Alarm Time in Hours
(i.e. 5 min. = 0.084 Hours)
[ ]
= __________
Add Standby and Alarm Load for Required Ampere Hour Battery __________
Multiplying by derating factor of 1.2 X1.2
Total Ampere Hour Battery
1
= __________