411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D
Appendix F Canadian Applications
This section illustrates the connection of the 411UDAC Digital Alarm Communicator/Transmitter (DACT) to an
FACP for Canadian Applications. The following conditions must be adhered to in order to comply with Canadian
requirements.
1. Only one FACP can be connected to the 411UDAC DACT.
2. Phone lines must exit the building in separate directions.
3. The 411UDAC DACT relay #1 must be enabled [refer to “Output Relay #1 Enable (85)” on page 49] and must
be programmed to activate on DACT trouble [refer to “Output Relay #1 Function Selections (86)” on page
49].
4. The Auxiliary Trouble Input wiring from the 411UDAC DACT must be in conduit and in the same room as
the FACP and DACT.
411UDAC
FACP
Auxiliary Trouble Input
(nonsupervised, power-limited)
Channel 4 (2.2k ELR)
-24 VDC nonresettable power from FACP
Relay Output (DACT
Trouble) from 411UDAC
FACP Alarm Relay
FACP ATrouble Relay
FACP Supv. Relay
2.2K ELRs P/N 27070