SMB Gateway GW-1000-WE/GW-1000-NWE INSTALLATION INSTRUCTIONS
Gateway GW-1000-WE/GW-1000-NWE PRODUCT DATA Disclaimer BACnet® is a registered trademark of ASHRAE Inc. FEATURES All images used in this document are for illustrative purposes only and may not match the actual product. • Integrated with Small and Medium Building Administrator Supervisor Dashboard (built on Honeywell Forge cloud platform). • Configurable via the Honeywell Connect Mobile app.
GATEWAY (GW-1000-WE/GW-1000-NWE) INTERFACES AND TERMINALS 4 3 2 1 12 11 10 6 13 14 5 9 8 7 NOTE: *All RS485 interfaces, USB interfaces, RJ11 interface, Rx and Tx LEDs are for future use. Table 1.
GATEWAY (GW-1000-WE/GW-1000-NWE) Table 1.
GATEWAY (GW-1000-WE/GW-1000-NWE) TECHNICAL DATA Table 5. Standards System Transformer System Data Table 2. System Data Operating Voltage (AC) 19 to 29 Vac (50/60Hz) Operating Voltage (DC) 19 to 29 Vdc Overvoltage Protection Operating Environment Table 6. Operating Environment Protected against overvoltages of max. 29 Vac or 40 Vdc. Terminals are protected against short-circuiting. Power Consumption Table 3. Power Consumption Power Gateway GW-1000-WE/GW1000-NWE 24 Vac 24 Vdc Max. 35VA Max.
GATEWAY (GW-1000-WE/GW-1000-NWE) Communication Baud Rates Gateway Parameters Table 7. Communication Baud Rates Table 8. Gateway Parameters Ethernet 10/100/1000 Mbit/s, RJ45 Max number of points 3000 BACnet MSTP 9.6, 19.2, 38.4, 76.8, 115.2 Kbps Max trend retention Wi-Fi 802.11b: up to 11Mbps 802.11g: up to 54Mbps 802.
GATEWAY (GW-1000-WE/GW-1000-NWE) Accessories Part Numbers These accessories are available by separate order. Table 10. Accessories Part Number Description GW-TCVR Replacement Terminal Covers (Small) (Pack Quantity of 4) GW-EXT-TCVR Extended Terminal Covers (Large) (Pack Quantity of 4) ANT-REM Remote Antennas with adhesive magnetic foot for wireless communication. 1.5 meter (4.9 feet) cable length for remote mounting of the antenna.
GATEWAY (GW-1000-WE/GW-1000-NWE) DIMENSIONS GW-1000-WE/GW-1000-NWE 145.8 mm (5.744") 45 mm (1.772") 110 mm (4.331") 135 mm (5.315") 52 mm (2.047") 59 mm (2.323") GENERAL SAFETY INFORMATION • • When performing any work (installation, mounting, start-up), all manufacturer instructions and in particular the Installation and Commissioning Instructions (EN1B-0077IE10) are to be observed. • GW-1000-WE/GW-1000-NWE Gateway must be installed and mounted only by authorized and trained personnel.
GATEWAY (GW-1000-WE/GW-1000-NWE) Professional Installation Table 12. Safety Information as per EN60730-1 • This device must be professionally installed, this should be noted on grantee. • To maintain compliance, only the antenna types that have been tested shall be used, which listed in “Remote Antenna Part Numbers” on page 6. This device requires a significant technology engineering expertise towards understanding of the tools and relevant technology, not readily available to average consumer.
GATEWAY (GW-1000-WE/GW-1000-NWE) CONTENTS General Safety Information ............................................... 3 Technical Data ....................................................................... 4 Electrical Data ............................................................................... 4 Power Consumption ................................................................... 4 Current Consumption ................................................................ 4 Operational Environment ......
GENERAL SAFETY INFORMATION It is suitable for panel rail mounting on 35 mm standard panel rail (both horizontal and vertical rail mounting possible). • When performing any work (installation, mounting, start-up), all manufacturer instructions and in particular the Installation and Commissioning Instructions (EN1B-0205IE10) are to be observed. • Gateway may be installed and mounted only by authorized and trained personnel. • Rules regarding electrostatic discharge should be followed.
GATEWAY (GW-1000-WE/GW-1000-NWE) TECHNICAL DATA Table 5. Operational Environment Electrical Data Table 2. Electrical Data RFI, EMI Residential, commercial, and light-industrial environments MTBF (Mean Time Between Failure) 11.5 years Operating Voltage (AC) 19 to 29 Vac (50/60Hz) Operating Voltage (DC) 19 to 29 Vdc Screw-type Terminals 2.5 mm2 IP Address Overvoltage Protection Protected against overvoltages of max. 29 Vac or 40 Vdc, terminals are protected against short-circuiting. 192.168.
INTERFACES 4 3 2 1 12 11 10 6 13 14 5 9 8 7 Fig. 1. GW-1000-WE/GW-1000-NWE Gateway NOTE: *All RS485 interfaces, USB interfaces, RJ11 interface, Rx and Tx LEDs are for future use. Table 8.
GATEWAY (GW-1000-WE/GW-1000-NWE) Table 8.
Table 9. Main LED Pattern LED behavior Visual Meaning Blink every 0.2S Green Firmware download or device configuration is in progress Blink every 0.2S Red Total communication failure Three Blinks in 1.5 second interval and then Pause for 2 sec Red Internet/Cloud connection failure 2 Red Blinks and Pause OS booting Yellow Slow Blink every 1 sec Wi-Fi connection is in progress after device boot-up.
GATEWAY (GW-1000-WE/GW-1000-NWE) Reset Button Honeywell Connect Mobile App The GW-1000-WE/GW-1000-NWE gateway has a reset button to reset the device to factory default. The user should push the button for 20 seconds to reset the Gateway. After reset, the Gateway will restart two times. The reset performs the following operations and completes in three minutes. For more information, refer to the Small and Medium Building Administrator Deploy App Setup guide (3100451M).
Switch Mode Power Supply To reduce overall current consumption, the GW-1000WE/GW-1000-NWE gateway can be powered by a switch mode dc power supply (rather than by a transformer). CAUTION Observe the precautions for handling electrostatic devices. Wiring Terminals Fusing The choice of appropriate fusing is dependent upon the given connection scenario (i.e., cable lengths and the use of a primary and/or secondary transformer) and upon the type of connected bus. Table 14.
GATEWAY (GW-1000-WE/GW-1000-NWE) WIRING CONNECTIONS 24V0 FGND 24V~ CH1+ RS485+ RS485- GND_ISO CH1- GND1 Gateway to MultiTech LoRaWAN hub connection 5V_ISO Isola on Barrier Mul Tech LoRaWAN Hub Ethernet 2 Ethernet 1 TX 5VDC RX Ethernet 5V GND GW-1000-WE/ GW-1000-NWE WARNING Do not connect the MultiTech LoRaWAN Hub to Ethernet 1 If connected to Ethernet 1 mistakenly, then restart the MultiTech LoRaWAN Hub before connecting to Ethernet 2 31-00426 | Rev.
WIRELESS CONNECTIVITY Connectivity Frequency Range Table 16. Connectivity Frequency Range Connectivity Medium Frequency Range E.I.R.P for CE E.I.R.P for FCC/IC Bluetooth 2400 MHz2483.5 MHz 20 mW 20 mW Wi-Fi 2.4 GHz 2400 MHz2483.5 MHz 100 mW 320 mW harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation.
GATEWAY (GW-1000-WE/GW-1000-NWE) DIMENSIONS GW-1000-WE/GW-1000-NWE Gateway 145.8 mm (5.744") 45 mm (1.772") 110 mm (4.331") 135 mm (5.315") 59 mm (2.323") 31-00426 | Rev.10-20 12 52 mm (2.
APPENDIX: EARTH GROUNDING Functional EMC Grounding • Use a cable as short as possible for grounding: min 1.5 mm2 (16 AWG). • For connection details, refer to the following example. Gateway and SELV In order to avoid distribution of noise or earth ground potential differences over networks or other connections, the GW-1000-WE/GW-1000-NWE gateway is designed to comply with SELV (Safety Extra Low Voltage). Furthermore, SELV offers the greatest possible safety against electrical impact.
GATEWAY (GW-1000-WE/GW-1000-NWE) GATEWAY PART NUMBERS Table 17. Gateway Part Numbers Part Number Description GW-1000-WE Wireless Gateway with European and Latin American conformance GW-1000-NWE Wireless Gateway with North American conformance Accessories Part Numbers These accessories are available by separate order. Table 18.
Remote Antenna Part Numbers Table 19. Remote Antenna Part Numbers Antenna Part Number Vendor Name Type Gain CA #ANTT935-4 ADAM External 2.4 GHz: 2.9dbi ANT-DB1-LCD-SMA LINX External 2.4 GHz: 2.8dbi ARY113-0012-004-00 WIESON External 2.4 GHz: -0.31dbi Declaration Transmitter Antenna (From Section 6.
GATEWAY (GW-1000-WE/GW-1000-NWE) TECHNICAL LITERATURE Table 20. Technical Literature Title Product Literature Number Contents GW-1000-WE/GW-1000-NWE Gateway Datasheet 31-00424 Product data of the device. GW-1000-WE/GW-1000-NWE Gateway Mounting Instructions 31-00425 Describes the mechanical mounting of the device. IO-10MIXR-WE/IO-10MIXR-NWE Smart IO Datasheet 31-00427 Product data of the device.