Users Manual

GATEWAY (GW-1000-WE/GW-1000-NWE)
31-00426 | Rev.10-20 4
TECHNICAL DATA
Electrical Data
Power Consumption
Current Consumption
Operational Environment
Default IP Address
Standards
Table 2. Electrical Data
Operating Voltage
(AC)
19 to 29 Vac (50/60Hz)
Operating Voltage
(DC)
19 to 29 Vdc
Screw-type Terminals 2.5 mm
2
Overvoltage
Protection
Protected against overvoltages
of max. 29 Vac or 40 Vdc,
terminals are protected
against short-circuiting.
Table 3. Power Consumption
Gateway
Power
24Vac 24Vdc
GW-1000-WE/GW-
1000-NWE
Max. 35VA Max. 15W
Table 4. Current Consumption
Gateway
Power
24Vac 24Vdc
GW-1000-WE/GW-
1000-NWE
1430mA 620mA
Table 5. Operational Environment
Ambient Operating
Temperature
0 to 50 °C (32 to 122 °F)
Ambient Operating
Humidity
5 to 95% relative humidity
(non-condensing)
Ambient Storage
Temperature
-28.9 to +70°C (-20 to 158 °F)
Ambient Storage
Humidity
5 to 95% relative humidity
(non-condensing)
Vibration Under
Operation
0.024” double amplitude (2 to
30 Hz), 0.6 g (30 to 300 Hz)
Dust, Vibration According to EN60730-1
RFI, EMI Residential, commercial, and
light-industrial environments
MTBF (Mean Time
Between Failure)
11.5 years
Table 6. Default IP Address
IP Address 192.168.2.1
(applicable only when Gateway is in
AP mode)
Net Mask 255.255.255.0
Table 7. Standards
Protection
Class
IP20
Product
Standards
CAN/CSA-E60730-1:02, Ethernet
Protocol version IEEE 802.3
Testing
Electrical
Components
IEC68
Certification UL60730-1
UL916
EN 60730-1
EN 60730-2-9
FCC Part15, Subpart B
CAN ICES-3 (B)/NMB-3(B)
BQB
RoHS II
REACH
System
Transformer
The system transformer(s) must be
safety isolating transformers
according to IEC 61558-2-6. In the
U.S.A. and Canada, NEC Class 2
transformers must be used.
Table 5. Operational Environment