Users Manual

GATEWAY (GW-1000-WE/GW-1000-NWE)
31-00424 | Rev.10-20 4
TECHNICAL DATA
System Data
Power Consumption
Current Consumption
Standards
Operating Environment
Table 2. System Data
Operating
Voltage (AC)
19 to 29 Vac (50/60Hz)
Operating
Voltage (DC)
19 to 29 Vdc
Overvoltage
Protection
Protected against overvoltages of
max. 29 Vac or 40 Vdc. Terminals are
protected against short-circuiting.
Table 3. Power Consumption
Gateway
Power
24 Vac 24 Vdc
GW-1000-WE/GW-
1000-NWE
Max. 35VA Max. 15W
Table 4. Current Consumption
Gateway
Power
24 Vac 24 Vdc
GW-1000-WE/GW-
1000-NWE
1430mA 620mA
Table 5. Standards
Protection
Class
IP20
Product
Standards
CAN/CSA-E60730-1:02, Ethernet
Protocol version IEEE 802.3
Testing
Electrical
Components
IEC68
Certification UL60730-1
UL916
EN 60730-1
EN 60730-2-9
FCC Part15, Subpart B
CAN ICES-3 (B)/NMB-3(B)
BQB
RoHS II
REACH
System
Transformer
The system transformer(s) must be
safety isolating transformers
according to IEC 61558-2-6. In the
U.S.A. and Canada, NEC Class 2
transformers must be used.
Table 6. Operating Environment
Ambient
Operating
Temperature
0 to 50 °C (32 to 122 °F)
Ambient
Operating
Humidity
5 to 95% relative humidity (non-
condensing)
Storage
Temperature
-28.9 to +70 °C (-20 to 158 °F)
Ambient
Storage
Humidity
5 to 95% relative humidity (non-
condensing)
Vibration
Under
Operation
0.024” double amplitude (2 to 30 Hz),
0.6 g (30 to 300 Hz)
Dust, Vibration According to EN60730-1
RFI, EMI Residential, commercial, and light-
industrial environments
MTBF (Mean
Time Between
Failure)
11.5 years
Table 5. Standards