Installation

24
Function Number
Setting
Displayed Description
1 System Type
1 Humidifier
2 Dehumidifier
4 Control Mode
Automatic Mode is Default when Outdoor Sensor Detected
Manual Mode is Default when NO Outdoor Sensor Detected
1 Automatic
2 Manual
5 Automatic Mode RH% (Hum)
This is the humidity setpoint (RH%) the control will operate to.
The homeowner does not change this and will only need to set
the appropriate window protection setting.
Range: 20%-60%
Default = 35%
11 Automatic Mode Humidity Boost
Increases Preset RH% (#5) when user sets window protection
to 11.
0 OFF
5% 5%
10% 10%
17 Automatic Mode High Temp Shut-Off
Turns humidifier OFF when Outdoor Temperature is greater
than selected setting.
Range: 40° - 90°
0 = OFF
Default = 65°
19 High Hum Limit
Range: 10% - 90%
Default = 60%