Install Instructions

H7625A, H7635A, H7626A, H7636A SERIES 2000 HUMIDITY/TEMPERATURE SENSORS
7 62-0327—03
Table 3. Test and Calibration Settings (8-Switch Block).
* = Switch setting does not affect output
** = This switch needs to be activated first
— = Indicates OFF
Setting 12345678
4-20mA Output ————————
0-5 VDC Output —————OnOn
0-10 VDC Output ——————OnOn
0% RH Output On———————
50% RH Output —On——————
100% RH Output ——On—————
Increment RH Output ———On**On———
Decrement RH Output ———On**—On——
Reset to Original Calibration ———On**OnOn——
Reverse or Direct Acting On On** On
Reverse or Direct Acting Reset On On** On On