Submittal Sheet

Table Of Contents
H7625, H7635, H7655 SERIES 2000 HUMIDITY/TEMPERATURE SENSORS
3 63-4521—01
Fig. 2. Duct-mount sensor dimensions in in. (mm).
TYPICAL SPECIFICATION
Fig. 3. Outdoor-mount sensor dimensions in in. (mm).
3-15/16 (100)
2-1/4
(57)
3/4
(19)
7-1/8
(182)
2-1/4
(57)
1-1/16
(27)
KNOCKOUTS (4)
3-3/4
(95)
M22583A
3/4
(19)
Humidity transducer shall be accurate to ±2%, ±3%,
or ±5% RH (whichever is specified) across the rela-
tive humidity range from 20-95%, NIST traceable
calibration.
Humidity transducers shall be calibrated at three dif-
ferent points across the RH range.
Interchangeability of output between humidity trans-
ducers shall be within ±3%.
Each humidity transducer shall have selectable
4to20mA, 0to10Vdc, or 0to5Vdc output.
Each humidity transducer shall have the option for
field calibration using zero and span potentiometers,
and toggle switches to increment or decrement the
RH value in steps of 0.5% RH.
Accuracy of the humidity transducers shall not be
adversely affected by condensation.
3-3/4
(95)
M22584
6-1/2
(165)
3-15/16 (100)
2-1/4
(57)
3/4
(19)
4-11/16 (119)
KNOCKOUTS
(3)
7/8
(22)
1-3/8
(36)