HC900 Hybrid Controller Installation and User Guide

Appendix B Installation of Remote Termination Panels (RTPs) - Analog Input
Revision 5 HC900 Hybrid Controller Installation and User Guide 189
9/03
8 Point Analog Input
Step Action
1 2 3 7 8 94 5 6 10 11 12 13 17 18 1914 15 16 20
21 22 23 27 28 2924 25 26 30 31 32 33 37 38 3934 35 36 40
Input 1 Input 2 Input 3 Input 4
Input 6
Input 7
Input 8
Slidewire
Slidewire
Slidewire
Slidewire
Slidewire
Slidewire
Input 5
Slidewire
Slidewire
R
F
R
FFF
F
F
F
F
R
R
RR
R
R
Note:
You must set switches 1- 8
for Ohms
.
1 2 3 7 8 94 5 6 10 11 12 13 17 18 1914 15 16 20
21 22 23 27 28 2924 25 26 30 31 32 33 37 38 3934 35 36 40
1 2 3 7 8 94 5 6 10 11 12 13 17 18 1914 15 16 20
21 22 23 27 28 2924 25 26 30 31 32 33 37 38 3934 35 36 40
Input 1 Input 2 Input 3 Input 4
Input 6
Input 7
Input 8
Slidewire
Slidewire
Slidewire
Slidewire
Slidewire
Slidewire
Input 5
Slidewire
Slidewire
R
F
R
FFF
F
F
F
F
R
R
RR
R
R
Note:
You must set switches 1- 8
for Ohms
.
Figure 67 Slidewire feedback connections for actuators
Analog Input accuracy specification
Range AI Module Accuracy RTP + Cable Accuracy
AI Module + RTP
Accuracy
100 Plat. RTD ±0.1% of Range ±0.04% Range (0.357°C) ±0.14% of Range
JIS RTD
±0.1% of Range ±0.12% Range (0.824°C) ±0.22% of Range
10 Cu. RTD ±0.1% of Range ±0.57% Range (1.540°C) ±0.67% of Range
200 OHMS ±0.1% of Range ±0.07% Range (0.140) ±0.17% of Range
0-10mV LINEAR
±0.1% of Range ±0.04% Range (0.004mV) ±0.14% of Range