Technical data
Input/output voltage 230 VAC, 50 Hz
Power consumption Max. 1750VA with
connected pump (max. 6A)
Pump relay Switching contact
230VAC, max. 6A (not
floating); cosϕ ≥ 0.7
Boiler feedback relay 42 VAC; 1 V < U 42 V;
1mA < I 100 mA; cosϕ = 1
Thermal actuators 2.7 A max. for 1s;
200mA; cosϕ ≥ 0.95
Ambient temperature 0 to 50°C
Storage temperature -20 to +70 °C
Humidity 5 to 93% relative humidity
Radio communication SRD (868,0...870,0)MHz
RX Class 2
Range Typically 30 m, one floor
Dimensions 350 x 82 x 52mm
(W x H x D)
Weight 1 kg
Fuse Ceramic fuse 5 x 20mm,
230VAC; 2.5A; fast
Material LOW
Degree of protection IP30
Fire class V0
Declaration of conformity
Honeywell hereby declares that HCE80(R) / HCC80(R)
complies with the basic requirements and other
relevant regulations of guideline 1999/5/EC.
The declaration of conformity of the product
can be requested from the manufacturer.
Note for non-EU countries:
This product may only be used
if operation in the 868 MHz
frequency band is permissible.
!
Device and function definition in
accordance with EN 60730-1
• Purpose of the device is temperature controlling
• Device fulfils Protection class 1,
EN60730-1, EN60730-2-9
• Independently installable electronic
control system with fixed installation
• Type of action is Type 1.B (pump relay)
and Type1.C (thermal actuator)
• Temperature
for ball-thrust hardness test for housing components:
75°C and
for live parts such as terminals: 125 °C
• EMC emitted interference test at 230VAC
+10/-15%, 1750VA maximum
• Pollution severity is 2
• Rated voltage is 4000V (corresponding
to Overvoltage category III)
WEEE directive 2012/19/EC
Waste Electrical and Electronic Equipment directive
• At the end of the product life dispose of the packaging
and product in a corresponding recycling centre.
• Do not dispose of the unit with the
usual domestic refuse.
• Do not burn the product.
• Remove the batteries.
• Dispose of the batteries according to the local statutory
requirements and not with the used domestic refuse.
Appendix
continued