Spec Sheet

GENERATOR OUTPUT VOLTAGE/kW - 60 Hz
kW LPG Amp LPG kW Nat. Gas Amp Nat. Gas CB Size (Both)
HG022
120/240 V, 1Ø, 1.0 pf 22 92 22 92 100
120/208 V, 3Ø, 0.8 pf 22 76 22 76 80
120/240 V, 3Ø, 0.8 pf 22 66 22 66 80
HG027
120/240 V, 1Ø, 1.0 pf 27 113 25 104 125
120/208 V, 3Ø, 0.8 pf 27 94 25 87 100
120/240 V, 3Ø, 0.8 pf 27 81 25 75 90
HG032
120/240 V, 1Ø, 1.0 pf 32 133 32 133 150
120/208 V, 3Ø, 0.8 pf 32 111 32 111 125
120/240 V, 3Ø, 0.8 pf 32 96 32 96 100
277/480 V, 3Ø, 0.8 pf 32 48 32 48 60
HG038
120/240 V, 1Ø, 1.0 pf 38 158 38 158 175
120/208 V, 3Ø, 0.8 pf 38 132 38 132 150
120/240 V, 3Ø, 0.8 pf 38 114 38 114 125
277/480 V, 3Ø, 0.8 pf 38 57 38 57 60
HG048
120/240 V, 1Ø, 1.0 pf 48 200 48 200 200
120/208 V, 3Ø, 0.8 pf 48 167 48 167 175
120/240 V, 3Ø, 0.8 pf 48 144 48 144 150
277/480 V, 3Ø, 0.8 pf 48 72 48 72 80
22 • 27 • 32 • 38 • 48 kW Operating Data
3
SURGE CAPACITY IN AMPS
Voltage Dip @ < .4 pf
15% 30%
HG022
120/240 V, 1Ø 55 135
120/208 V, 3Ø 40 92
120/240 V, 3Ø 35 80
HG027
120/240 V, 1Ø 62 170
120/208 V, 3Ø 70 120
120/240 V, 3Ø 61 103
HG032
120/240 V, 1Ø 75 180
120/208 V, 3Ø 87 210
120/240 V, 3Ø 75 182
277/480 V, 3Ø 36 87
HG038
120/240 V, 1Ø 75 180
120/208 V, 3Ø 87 210
120/240 V, 3Ø 75 182
277/480 V, 3Ø 36 87
HG048
120/240 V, 1Ø 85 195
120/208 V, 3Ø 90 218
120/240 V, 3Ø 78 189
277/480 V, 3Ø 36 87
ENGINE FUEL CONSUMPTION
Natural Gas Propane
(ft³/hr) (m³ /hr) (gal/hr) (l/hr) (ft³/hr)
HG022
Exercise cycle 42 1.2 0.44 1.7 16
25% of rated load 100 2.8 1.1 4.2 40
50% of rated load 190 5.4 2.1 7.8 75
75% of rated load 255 7.2 2.8 10.5 101
100% of rated load 316 9 3.4 13 125
HG027
Exercise cycle 42 1.2 0.44 1.7 16
25% of rated load 108 3.1 1.2 4.5 43
50% of rated load 197 5.6 2.1 8.1 78
75% of rated load 287 8.2 3.1 11.8 114
100% of rated load 359 10.2 3.9 14.8 143
HG032
Exercise cycle 79 2.2 0.8 3.2 30
25% of rated load 144 4.1 1.7 6.3 60
50% of rated load 226 6.4 2.7 10.3 97
75% of rated load 298 6.4 3.7 13.9 132
100% of rated load 375 10.6 4.6 17.5 166
HG038
Exercise cycle 83 2.3 0.9 3.2 31
25% of rated load 162 4.6 1.7 6.6 62
50% of rated load 255 7.2 2.9 10.8 103
75% of rated load 345 9.8 4 15 142
100% of rated load 437 12.4 5.2 19 185
HG048
Exercise cycle 95 2.7 1 3.9 38
25% of rated load 204 5.8 2.16 8.5 82
50% of rated load 392 11.1 4.14 15.7 151
75% of rated load 547 15.5 5.8 22.8 220
100% of rated load 756 21.5 7.96 31.3 302
STANDBY RATING: Standby ratings apply to installations served by a reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage. There
is no overload capability for this rating. Ratings are in accordance with ISO-3046-1. Design and specifications are subject to change without notice.
Note: Fuel pipe must be sized for full load.
For Btu content, multiply ft³/hr x 2520 (LP) or ft³/hr x 1000 (NG)
For megajoule content, multiply m³/hr x 93.15 (LP) or m³/hr x 37.26 (NG)
Refer to "Emissions Data Sheets" for maximum fuel flow for EPA and
SCAQMD permitting purposes.