Spec Sheet

2119
[83.4]
OVERALL LENGTH
1212 [47.7]
DOOR TYP
888 [35.0]
OVERALL WIDTH
2026 [79.8] TYP
58
[2.3]
TYP
47
[1.8]
318
[12.5]
65
[2.6]
1168 [46.0]
OVERALL
HEIGHT
843 [33]
CENTER OF GRAVITY
(SEE NOTE 5)
WEIGHT DATA
ENGINE/KW
ENCLOSURE
MATERIAL
WEIGHT
GENSET ONLY
KG [LBS]
WEIGHT
SHIPPING SKID
KG [LBS]
SHIPPING WEIGHT
KG [LBS]
4.5L/48KW AL 808 [1781] 51 [112] 859 [1893]
SERVICE ITEM 4.5L
OIL FILL CAP LEFT SIDE
OIL DIP STICK LEFT SIDE
OIL FILTER LEFT SIDE
OIL DRAIN HOSE RIGHT SIDE
RADIATOR DRAIN HOSE RIGHT SIDE
COOLANT RECOVERY BOTTLE RIGHT SIDE
RADIATOR FILL CAP ROOF TOP
AIR CLEANER ELEMENT LEFT SIDE
SPARK PLUGS LEFT SIDE
MUFFLER SEE NOTE 11
DRIVE BELT EITHER SIDE
BATTERY LEFT SIDE
NOTES:
1. MINIMUM RECOMMENDED CONCRETE PAD SIZE IS 6" OFFSET OF OVERALL LENGTH
AND WIDTH OF GENERATOR. {1193.8 (47") WIDE X 2423.2 (95.4") LONG}. REFERENCE
INSTALLATION GUIDE SUPPLIED WITH THE UNIT FOR CONCRETE PAD GUIDELINES.
REFERENCE MANUFACTURER'S SPECIFICATIONS IF USING ENGINEERED, PREFABRICATED SLABS.
2. ALLOW SUFFICIENT ROOM ON ALL SIDES OF THE GENERATOR FOR MAINTENANCE
AND SERVICING. THIS UNIT MUST BE INSTALLED IN ACCORDANCE WITH CURRENT
APPLICABLE NFPA 37 AND NFPA 70 STANDARDS AS WELL AS ANY OTHER FEDERAL,
STATE, AND LOCAL CODES.
3. CONTROL PANEL / CIRCUIT BREAKER INFORMATION:
- SEE SPECIFICATION SHEET OR OWNERS MANUAL
- ACCESSIBLE THROUGH CUSTOMER ACCESS ASSEMBLY DOOR ON REAR OF GENERATOR.
4. REMOVE THE REAR ENCLOSURE COVER PANEL TO ACCESS
THE STUB-UP AREAS AS FOLLOWS:
- HIGH VOLTAGE CONNECTION INCLUDING AC LOAD LEAD CONDUIT CONNECTION
NEUTRAL CONNECTION, BATTERY CHARGER 120 VOLT AC (0.5 AMP MAX) CONNECTION.
- LOW VOLTAGE CONNECTION INCLUDING TRANSFER SWITCH CONTROL WIRES.
5. CENTER OF GRAVITY AND WEIGHT MAY CHANGE DUE TO UNIT OPTIONS.
6. BOTTOM OF GENERATOR SET MUST BE ENCLOSED TO PREVENT PEST INTRUSION AND
RECIRCULATION OF DISCHARGE AIR AND/OR IMPROPER COOLING AIR FLOW.
7. REFERENCE OWNERS MANUAL FOR LIFTING WARNINGS.
8. MOUNTING BOLTS OR STUDS TO MOUNTING SURFACE SHALL BE 5/8-11 GRADE 5
(USE STANDARD SAE TORQUE SPECS)
9. MUST ALLOW FREE FLOW OF INTAKE AIR, DISCHARGE AIR AND EXHAUST. SEE SPEC
SHEET FOR MINIMUM AIR FLOW AND MAXIMUM RESTRICTION REQUIREMENTS.
10. GENERATOR MUST BE INSTALLED SUCH THAT FRESH COOLING AIR IS AVAILABLE
AND THAT DISCHARGE AIR FROM RADIATOR IS NOT RECIRCULATED.
11. EXHAUST MUFFLER ENCLOSED WITHIN GENERATOR ENCLOSURE,
REMOVE FRONT PANEL TO ACCESS.
TOP VIEW
LEFT SIDE VIEW
REAR VIEW
RIGHT SIDE VIEW
RADIATOR/EXHAUST
DISCHARGE AIR
(BOTH SIDES)
AIR INTAKE
(BOTH SIDES)
REFERENCE OWNERS MANUAL
FOR PERIODIC REPLACEMENT
PARTS LIST
DIMENSIONS: MM [INCH]
EXHAUST MUFFLER
ENCLOSED WITHIN
GENERATOR ENCLOSURE
RADIATOR/EXHAUST
DISCHARGE AIR
CUSTOMER ACCESS
ASSEMBLY, CONTROL
PANEL ACCESS
BATTERY CHARGER
LOCATED WITHIN
SEE NOTE 4
REAR ENCLOSURE
COVER PANEL
SEE NOTE 4
CIRCUIT BREAKER
SEE NOTE 3
VICE ACTION LATCH
ONE PER DOOR
ONE LIFT OFF DOOR PER
SIDE OF GENERATOR
FUEL LINE CONNECTION
1-1/4" NPT FEMALE TEE
THROUGH BASEFRAME OPENING
REMOVE COVER
FOR ACCESS TO
RADIATOR FILL
CAP
BATTERY 12V
GROUP 27F
NEGATIVE GROUND
P/N G058665
Drawing A0000293718 Rev B (1 of 2)
48 kW Installation Layout