60 / 80 kW Installation Layout
Drawing A0000293264 Rev B (1 of 2)
4 3 2 1
4 3 1
A
B
A
B
1041.4 [41.00]
DOOR WIDTH TYP
960
[37.8]
CG (SEE NOTE 5)
2481 [97.7]
OVERALL LENGTH
109
[4.3]
1241 [48.9]
OVERALL
HEIGHT
63.5 [2.5]
LIFTING EYE
(4X)
47 TYP
[1.8]
2357 [92.8] TYP
964 [38.0]
OVERALL WIDTH
68 TYP
[2.7]
350
[13.8]
SERVICE ITEM 4.5L
OIL FILL CAP LEFT SIDE
OIL DIP STICK LEFT SIDE
OIL FILTER LEFT SIDE
OIL DRAIN HOSE LEFT SIDE
RADIATOR DRAIN HOSE RIGHT SIDE
COOLANT RECOVERY BOTTLE RIGHT SIDE
RADIATOR FILL CAP ROOF TOP
AIR CLEANER ELEMENT EITHER SIDE
SPARK PLUGS LEFT SIDE
MUFFLER SEE NOTE 11
FAN BELT EITHER SIDE
BATTERY LEFT SIDE
WEIGHT DATA
ENGINE/KW
ENCLOSURE
MATERIAL
WEIGHT
GENSET ONLY
KG [LBS]
WEIGHT
SHIPPING SKID
KG [LBS]
SHIPPING WEIGHT
KG [LBS]
4.5L/60KW AL 857 (1890) 79 [175] 936 (2064)
4.5L/80KW AL 903 (1990) 79 [175] 983 (2165]
TITLE
INSTALL G4.5L G26 60-80KW C3
ISSUE DATE:
SIZE CAGE NO DWG NO
A0000293264
REV
B
N/A
B
SCALE
0.035
WT-KG SHEET
1 of 2
GENERAC POWER SYSTEMS OWNS THE COPYRIGHT OF THIS DRAWING
WHICH IS SUPPLIED IN CONFIDENCE AND MUST NOT BE USED FOR
ANY PURPOSE OTHER THAN FOR WHICH IT IS SUPPLIED WITHOUT
THE EXPRESS WRITTEN CONSENT OF GENERAC POWER SYSTEMS.
c GENERAC POWER SYSTEMS 2013
ELECTRONICALLY APPROVED
INSIDE WINDCHILL
DRAWING CREATED FROM PRO/ENGINEER
3D FILE. ECO MODIFICATION TO BE
APPLIED TO SOLID MODEL ONLY.
SH
1/2
REV
B
WINDCHILL VERSION
B.3
NOTES:
1. MINIMUM RECOMMENDED CONCRETE PAD SIZE: (6" LARGER PER SIDE THAN GENERATOR)
1269 (50") WIDE 2786 (110") LONG.
REFERENCE INSTALLATION GUIDE SUPPLIED WITH UNIT FOR CONCRETE PAD GUIDELINES.
2. ALLOW SUFFICIENT ROOM ON ALL SIDES OF THE GENERATOR FOR MAINTENANCE
AND SERVICING. THIS UNIT MUST BE INSTALLED IN ACCORDANCE WITH CURRENT
APPLICABLE NFPA 37 AND NFPA 70 STANDARDS AS WELL AS ANY OTHER FEDERAL,
STATE, AND LOCAL CODES.
3. CONTROL PANEL / CIRCUIT BREAKER INFORMATION:
- SEE SPECIFICATION SHEET OR OWNERS MANUAL
- ACCESSIBLE THROUGH CUSTOMER ACCESS ASSEMBLY ON REAR OF GENERATOR.
4. INSIDE STUB-UP AREA FOR AC LOAD LEAD CONDUIT CONNECTION, NEUTRAL CONNECTION,
BATTERY CHARGER 120 VOLT AC (.5 AMP MAX) CONNECTION AND ACCESS TO TRANSFER
SWITCH CONTROL WIRES. REMOVE REAR COVER FOR ACCESS.
5. CENTER OF GRAVITY AND WEIGHT MAY CHANGE DUE TO UNIT OPTIONS.
6. BOTTOM OF GENERATOR SET MUST BE ENCLOSED TO PREVENT PEST INTRUSION AND
RECIRCULATION OF DISCHARGE AIR AND/OR IMPROPER COOLING AIR FLOW.
7. REFERENCE OWNERS MANUAL FOR LIFTING WARNINGS.
8. MOUNTING BOLTS OR STUDS TO MOUNTING SURFACE SHALL BE 5/8-11 GRADE 5
(USE STANDARD SAE TORQUE SPECS)
9. MUST ALLOW FREE FLOW OF INTAKE AIR, DISCHARGE AIR AND EXHAUST. SEE SPEC
SHEET FOR MINIMUM AIR FLOW AND MAXIMUM RESTRICTION REQUIREMENTS.
10. GENERATOR MUST BE INSTALLED SUCH THAT FRESH COOLING AIR IS AVAILABLE
AND THAT DISCHARGE AIR FROM RADIATOR IS NOT RECIRCULATED.
11. REMOVE FRONT END PANEL TO ACCESS EXHAUST MUFFLER. ACCESS AVAILABLE
THROUGH DOORS TO FAN BELT.
EXHAUST MUFFLER
ENCLOSED WITHIN
GENERATOR ENCLOSURE
SEE NOTES 9, 10 & 11
DIMENSIONS: MM [INCH]
RADIATOR/EXHAUST
DISCHARGE AIR
RADIATOR/EXHAUST
DISCHARGE AIR
(BOTH SIDES)
AIR INTAKE
(BOTH SIDES)
LEFT VIEW
CIRCUIT BREAKER
SEE NOTE 3
REFERENCE OWNERS MANUAL
FOR PERIODIC REPLACEMENT
PART LISTINGS.
REAR ENCLOSURE
COVER PANEL
SEE NOTE 4
CUSTOMER ACCESS
ASSEMBLY, CONTROL
PANEL ACCESS
BATTERY CHARGER
LOCATED WITHIN
SEE NOTE 3 & 4
REAR VIEW
VICE ACTION LATCH
ONE PER DOOR
ONE LIFT OFF DOOR PER
SIDE OF GENERATOR
RIGHT VIEW
FUEL LINE CONNECTION
1-1/4" NPT FEMALE TEE
THROUGH BASE FRAME OPENING
RADIATOR DRAIN
TOP VIEW
BATTERY 12V
GRP 27F
NEGATIVE GROUND
P/N G058665
REMOVE COVER FOR
ACCESS TO RADIATOR
FILL CAP
OIL DRAIN