Spec Sheet

3
KW RATING (LP/NG)
60/60
ENGINE SIZE
2.4 Liter 4 cyl. inline
GENERATOR OUTPUT VOLTAGE/KW - 60Hz
kW LPG AMP CB Size
120/240V, 1-phase, 1.0 pf 60 250 300
120/208V, 3-phase, 0.8 pf 60 208 250
120/240V, 3-phase, 0.8 pf 60 180 200
277/480V, 3-phase, 0.8 pf 60 90 100
ENGINE FUEL CONSUMPTION (Natural Gas) (Propane)
Natural Gas
(ft
3
/hr.)
Propane
gal/hr ft
3
/hr
Exercise cycle 123 1.34 49.3
25% of rated load 267 2.7 101
50% of rated load 483 5.0 183
75% of rated load 672 7.0 255
100% of rated load* 862 9.0 327
For Btu content, multiply ft
3
/hr x 2520 (LP) or ft
3
/hr x 1000 (NG)
ENGINE COOLING
Air flow (inlet air including alternator and combustion air) ft
3
/min. 3,280
System coolant capacity US gal. 2.5
Heat rejection to coolant BTU/hr. 270,000
Max. operating air temp. on radiator °C (°F) 60 (150)
Max. ambient temperature °C (°F) 50 (140)
COMBUSTION AIR REQUIREMENTS
Flow at rated power 60 Hz cfm 180
SOUND EMISSIONS IN DBA
Exercising at 7 meters 65
Normal operation at 7 meters 72
EXHAUST
Exhaust flow at rated output 60 Hz cfm 494
Exhaust temp. at muffler outlet °F 1,050
ENGINE PARAMETERS
Rated synchronous RPM 60 Hz 3600
POWER ADJUSTMENT FOR AMBIENT CONDIIONS
Temperature Deration 3% for every 10 °C above - °C
1.65% for every 10 °F above - °F
25
77
Altitude Deration 1% for every 100 m above - m
3% for every 1000 ft. above - ft.
915
3000
RATING: All three phases units are rated at 0.8 power factor. All single phase units are rated at 1.0 power factor. STANDBY RATING: Standby ratings apply to installations served
by a reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage. There is no overload capability for this rating. Ratings are in
accordance with ISO-3046-1. Design and specifications are subject to change without notice.
Operating Data
Refer to “Emissions Data Sheets” for maximum fuel flow for EPA and SCAQMD permitting purposes.